![background image](http://html.mh-extra.com/html/abb/reta-01/reta-01_user-manual_209025.webp)
Quick start-up guide
25
Table 5. Drive configuration for Extended Speed Control
Drive parameter
Example setting for ACS800
10.01 EXT1 STRT/STP/DIR
COMM.CW
10.03 REF DIRECTION
REQUEST
11.03 EXT1 REF1 SELECT
COMM.REF
16.04 FAULT RESET SEL
COMM.CW
98.02 COMM. MODULE LINK
FIELDBUS
98.07 COMM PROFILE
GENERIC
51.01 MODULE TYPE
ETHERNET
51.02 COMM RATE
0 (Auto-negotiation)
51.03 DHCP
1 (Enabled)
51.04 - 51.07 IP ADDRESS
10.0.0.6
51.08 - 51.11 SUBNET MASK
255.255.255.0
51.12 - 51.15 GW ADDRESS
0.0.0.0
51.16 PROTOCOL
1 (AC/DC profile)