42
M N S - U P
SER V I C E M A N UA L
7.2
Clearance above MNS-Up system
The MNS-Up system uses forced ventilation to keep the UPS module temperature constant.
The air inlet to the UPS section is from the front, the air outlet is on the top. Therefore, there must be a clear-ance of at least
100 cm above the MNS-Up UPS section.
80 – 150 mm
80 – 150 mm
1000
mm
Figure 7-02 Clearance above MNS-Up system
7.3
Clearance behind MNS-Up system, clearance in front of the section
Clearance around MNS-Up sections must be:
Clearance to front
min. 1000 mm
Clearance to left side walls
min. 80 mm
Clearance to right side walls
min. 150 mm
Clearance to back wall
min. 80 mm
80 – 150 mm
80 – 150 mm
80
–
150
mm
1000
mm
Figure 7-03 Clearance above MNS-Up system
Summary of Contents for MNS-Up
Page 6: ... 01 Introduction ...
Page 8: ... 02 Safety first ...
Page 12: ... 03 General technical data ...
Page 16: ... 04 System description ...
Page 18: ... 05 Packing storage and transportation ...
Page 36: ... 06 Transport ...
Page 40: ... 07 Erecting ...
Page 47: ...47 ERECTING ...
Page 48: ... 08 MNS Up configuration ...
Page 52: ... 09 MNS Up Module installation ...
Page 55: ...55 MNS UP MODULE INSTALL ATION ...
Page 56: ... 10 Handling of EMC boards ...
Page 59: ...59 HANDLING OF EMC BOARDS ...
Page 60: ... 11 Communication boards ...
Page 62: ... 12 MNS 3 0 sections ...
Page 64: ... 13 Commissioning ...
Page 66: ... 14 Operating of MNS Up system ...
Page 68: ... 15 Tightening torques for screw connection in MNS Up ...
Page 72: ... 16 Spare parts ...
Page 74: ... 17 Onsite inspection and maintenance ...
Page 76: ... 18 Maintenance intervals ...
Page 81: ...81 MAINTENANCE INTERVALS ...
Page 83: ......