Packing, storage and transportation
5.1 General
MNS switchgear is shipped either in singIe section or in shipping units not exceeding 3 m in length depending on the type
of equipment instalIed and on the space available for handIing the switchgear at the erection site.
Maximum size of a shipping unit (length × width × height) in mm:
• Unpacked 3100 x 1300 x 2300
• Packed in crate 3300 x 1500 x 2590 (see also “3.1.1 Container shipment”)
The MNS-Up sections must be shipped as individual sections, due to their dimensions and weight.
In all cases the ACB must be transported separately from the section. It is not allowed to transport it within the section.
The ACB requires special attention during transport and handling. Please refer to original manuals 1SDH000999R0002 and
1SDH001000R0002, Chapter 2: Transport and checking on receipt.
Note: Shipping dimensions and weights here are approximate. These are meant to be used a guide only. Please refer to
project specific documentation.
!
Remove all ACBs from sections and transport them separately!
Module type
Protection circuit
Type
Module size
Withdrawable modules
Motor starters
Fuse
TOL / EOL
8E4 upto 24E
UMC100
M10x
Circuit breaker
TOL / EOL
UMC100
M10x
Energy distirbution
Fuse
SFU
8E4 upto 24E
Contactor feeder
Circuit breaker
MMS / MCCB
Contactor feeder
Plugin modules
Energy distirbution
Fuse
SFU
6E upto 24E
Contactor feeder
SlimLine
Circuit breaker
MMS / MCCB
Contactor feeder
Table 5-01
General overview of standard module solutions (customer specific solutions not mentioned)
If no special instructions are given by the customer, packing is carried out based on ABB shipping guidelines and a suitable
method of shipping is selected. Approximate weights for calculation are listed in below tables.
All weights for incoming feeders configured as below:
• Section weights are defined based on IP30-IP40 internal protection with bottom plate
• Section weight for EQ400 / EQ600 contains 200 mm main busbar area
• Section weight for EQ800 contains 400 mm main busbar area
• Section weights are defined with all possible CTs (measuring and protection), REF relay and SPD
• Section weights do not contain internal devices (except CTs, REF, SPD) and wiring
• Section weights do not contain side walls and main busbar end covers
All weights for couplers configured as below:
• Coupler weights do not contain internal devices (except CTs and REF) and wiring
• Coupler weights do not contain side walls and main busbar end cover
• The type of coupler with CTs utilizes different angle set (with more copper) to create place for CTs. If you use coupler
without CTs, the overall weight might be significantly lower.
Summary of Contents for MNS-Up
Page 6: ... 01 Introduction ...
Page 8: ... 02 Safety first ...
Page 12: ... 03 General technical data ...
Page 16: ... 04 System description ...
Page 18: ... 05 Packing storage and transportation ...
Page 36: ... 06 Transport ...
Page 40: ... 07 Erecting ...
Page 47: ...47 ERECTING ...
Page 48: ... 08 MNS Up configuration ...
Page 52: ... 09 MNS Up Module installation ...
Page 55: ...55 MNS UP MODULE INSTALL ATION ...
Page 56: ... 10 Handling of EMC boards ...
Page 59: ...59 HANDLING OF EMC BOARDS ...
Page 60: ... 11 Communication boards ...
Page 62: ... 12 MNS 3 0 sections ...
Page 64: ... 13 Commissioning ...
Page 66: ... 14 Operating of MNS Up system ...
Page 68: ... 15 Tightening torques for screw connection in MNS Up ...
Page 72: ... 16 Spare parts ...
Page 74: ... 17 Onsite inspection and maintenance ...
Page 76: ... 18 Maintenance intervals ...
Page 81: ...81 MAINTENANCE INTERVALS ...
Page 83: ......