Revision:
Language: Page:
A EN
18/37
1KHW001493-EN
Applying the second method to the configuration given below, a sinus with –9.0 dBm is fed into
remote equipment. Calculating the expected output level at local equipment with the formula above
results to:
L
out
= -9.0 dBm – (-4.00 dBr) + (-1.00 dBr)
The expected output level L
out
is just as applying the first method –6.0 dBm.
Equipment REMOTE
TELEOPERATION
Port AFx:
Disconnectable at CH1
Squelch:
Disabled
Reference signal:
600 Bd FSK
Reference signal level input:
-9.00 dBm (RMS)
Reference signal level output:
-9.00 dBm (RMS)
Weight of port:
0.71
Max. output level:
-7.00 dBm (PEP)
Relative input level:
-4.0 dBr
Relative output level:
-4.0 dBr
Input
filter:
None
Output
filter:
None
Equipment LOCAL
TELEOPERATION
Port AFx:
Disconnectable at CH1
Squelch:
Disabled
Reference signal:
600 Bd FSK
Reference signal level input:
-6.00 dBm (RMS)
Reference signal level output:
-6.00 dBm (RMS)
Weight of port:
0.71
Max. output level:
-4.00 dBm (PEP)
Relative input level:
-1.0 dBr
Relative output level:
-1.0 dBr
Input
filter:
None
Output
filter:
None
B.10.11
Teleoperation port AF1
If the port AF1 is not used for a telephony application and if the port is switched to
’On –
disconnectable
’ or ‘
On – non disconnectable
’, take the measurement as described in B.10.10.
B.10.12
Teleoperation port AF2
If the port is switched to
’On – disconnectable
’ or ‘
On – non disconnectable
’ take the
measurement as described in B.10.10.
B.10.13
Teleoperation port AF3
If the port is switched to
’On – disconnectable
’ or ‘
On – non disconnectable
’ take the
measurement as described in B.10.10.
B.10.14
Teleoperation port AF4
If the port is switched to
’On – disconnectable
’ or ‘
On – non disconnectable
’ take the
measurement as described in B.10.10.
B.10.15
Teleoperation AF4 used for ext. Teleprotection
After measurement of B.10.14 is done:
1.
Recalculate expected output level of AF4-OUT by adding the
NSD570 boost value
,
available in the configuration view (
View
/
Display Configuration
/
Effective boost
value ext. TPE1/2/3
).
2.
Activate the EXT-BOOST input at the remote equipment. If EXT-BOOST is configured as
‘inverted’, contacts at terminal, teleoperation, 9a-9b must be opened, otherwise closed.
3.
Take the measurement at AF4-OUT of local equipment.
Summary of Contents for ETL600
Page 4: ......
Page 32: ......
Page 126: ......
Page 176: ......
Page 206: ......
Page 216: ......
Page 226: ......
Page 264: ......
Page 268: ......
Page 276: ......
Page 284: ......
Page 308: ......
Page 324: ......
Page 346: ......
Page 348: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 380: ......