Revision:
Language: Page:
A EN
9/28
1KHW001495-EN
1. Select
Equipment
/
Commissioning and maintenance
/
Frequency response
/
APLC channel 1
,
APLC channel 2
or
APLC channel 3
, respectively.
2. In the following message box click
OK
and wait until measurement is done. The dialog
box
Select equalizer
appears.
C.7.2 Select
Equalizer
For each APLC channel, an equalizer can be selected under
Equipment
/
Commissioning and
maintenance
/
Select Equalizer
/
APLC channel 1
,
APLC channel 2
or
APLC channel 3
,
respectively.
1. Select the new equalizer:
In the field
New equalizer
, activate checkbox
Amplitude response equalisation only
.
2. External teleprotection equipment connected to ETL600 suffer from the additional delay
introduced by the equalizer. To reduce this delay, select type
None
or
Short
in the frame
New
equalizer
of the dialog box
Select equalizer
.
If delay is uncritical, select type
Middle
or
Long
in the frame
New
equalizer
of the dialog
box
Select equalizer
.
3. View the amplitude response by clicking
View
. If the amplitude response is acceptable,
go back to the
Select equalizer
dialog and select the viewed settings again. Download
the new equalizer settings by clicking
Download
. The equipment is reset now.
4. Wait until the equipment has restarted. The new equalizer is active now.
5. Exit.
C.8
Testing of R1BC, if present
For testing the R1BC, refer to the client specific setting instructions. Depending upon the
programmed criteria, activate the required alarms using the following table. Check the contact
closure of the programmed relays on R1BC. Restore the link after this test is completed.
Alarm on R1BC
Action to enforce the alarm
Warning LED on P4LT/P4LU
Activate a testtone in the ‘Adjust Tx RF level’ dialog box
Link alarm
Disconnect the RF line coaxial cable
Hardware (HW) alarm
Unplug the RF hybrid.
Interface alarm,
P4LT alarm / P4LU alarm
In case an external real time clock is configured and
connected: Disconnect the clock input to P4LT/P4LU.
In case no external real time clock is configured: Configure
it (dialog box ‘Configuration / System / Channel settings /
Event recorder: Ext. real time clock sync available’).
System alarm (i.e. cabinet alarm) Enforce either Link alarm or HW alarm
C.9
Configure Real Time Clock (RTC)
The real time clock has to be set to the actual date and time for proper operation of the event
recorder.
C.9.1
Setting real time clock
Setting the date and time using HMI600:
1. Open the menu
Equipment
/
Commissioning and maintenance
/
Eventrecorder
/
Set
Clock
.
2. In
the
Real Time Clock (RTC)
dialog box, check if PC time and PC date are correct.
3. Click
Download date/time to RTC
This sets the RTC to the given date and time.
4. Click
Upload date/time from RTC
The date and time displayed at Read RTC date & time part of the Real Time Clock (RTC)
box should be correct.
5. Click
Cancel
Summary of Contents for ETL600
Page 4: ......
Page 32: ......
Page 126: ......
Page 176: ......
Page 206: ......
Page 216: ......
Page 226: ......
Page 264: ......
Page 268: ......
Page 276: ......
Page 284: ......
Page 308: ......
Page 324: ......
Page 346: ......
Page 348: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 380: ......