ETL600 1KHW001489-EN
ABB Switzerland Ltd
to send the configuration commands to the modem. As these
commands differ depending on the type of the modems used, it is not
possible to specify a common configuration sequence for all modem
types. Please refer to your modem dealer or the example below for
further information.
Example:
Configuration of a ZyXEL U-90E Modem for connection to P4LT:
The modem is to be configured to the settings given by column
'Modem at P4LT' of the previous table with the help of the program
HyperTerminal. Connect the modem to one of the COM-ports of the
PC with a 9 pole 1:1 modem cable (female to male). In case the COM
port of the PC has a 25 pole RS-232 connector, an adapter (25 pole
female to 9 pole male) is needed. Start hyperterminal, select the
correct COM port and set the Baudrate to 57’600 Bd, connect to the
modem and type
at
. The modem should answer with
OK
. If your
modem returns garbage characters, retype
at
to adapt the modems
autobaud function to your baud rate. Do not send any other characters
(e.g. return) before
at
. This may disturb your modems autobaud
functionality. If you don't get any answer check your connections, the
modem settings and try again.
Now enter the following commands to setup the modem: The modem
should always send
OK
to confirm your entry.
Command: Explanation:
atz4
Load factory settings to get a defined modem setting.
ate0
Command echo off //delete.
ats0=1
Set the number of rings on which the modem will answer
automatically. S0=0 disables the auto answer.
ats20=3
Sets the speed of the serial interface to 57’600.
ats15=8
Set the modem to even parity and a character length of 11
(1 start bit , 8 data bits, 1 parity bit, 1 stop bit). The
terminal program now might receive some garbage
characters, which can be ignored.
Change the communication settings of the PC to the
modem using
Settings
/
Control panel
/
Modems
and of
hyperterminal to 57’600 Baud, 8 bits, even parity, 1 stop
bit. When typing
at
, the modem should answer with
OK
.
at&w0
Save the settings to profile 0.
atz0
Load profile 0 and set profile 0 as power-on profile.
4.4.3.2.2.
Configuration of HMI600
In the dialog box
Options
/
Communications…
, select
Phone
modem
, choose the correct
Modem
and set the
Timeout
to 3500ms
or higher.
User Interface Program
November 2005
4-7
Summary of Contents for ETL600
Page 4: ......
Page 32: ......
Page 126: ......
Page 176: ......
Page 206: ......
Page 216: ......
Page 226: ......
Page 264: ......
Page 268: ......
Page 276: ......
Page 284: ......
Page 308: ......
Page 324: ......
Page 346: ......
Page 348: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 380: ......