![ABB ETL600 Instruction Manual Download Page 298](http://html.mh-extra.com/html/abb/etl600/etl600_instruction-manual_5338298.webp)
Revision:
Language: Page:
A EN
12/37
1KHW001493-EN
B.8.2
Testing external real time clock synchronisation (if available)
The external clock source with IRIG-B format has to be connected to the IRIG-B port at the
frontplate of P4LT/P4LU via external cable V9OV.
Testing the external synchronisation using HMI600:
1.
Set the time on the PC a few hours back/forward
2. On
the
Equipment
menu point to
Commissioning and maintenance
menu point to
Eventrecorder
and click
Set Clock
.
3. Click
Download date/time to RTC
.
This sets the RTC to the wrong time.
4. Click
Upload date/time from RTC
.
The date and time displayed at Read RTC date &
time part of the Real time Clock (RTC) box should be correct and not correspond to the
PC-date/time setting.
5. Click
Cancel.
6.
Set the time on the PC back to the correct time
B.9
Testing of NSD600 with interface G4AI, if present
Designations and abbreviations used:
Designation Meaning
(T.22/..1)
Connector 1 of terminal block connected to rack position N22
B.9.1 Inputs
How to activate an input command depends on the jumper settings on G4AI.
•
G4AI input programmed as ‘contact and battery voltage’:
Inject a signal at input port with the voltage level U1 according to the jumper settings on
G4AI (24 VDC, 48 VDC, 110 VDC, 220 VDC)
•
G4AI input programmed as ‘contact only’:
Short circuit the input port
The way to activate the input port is the same for a Tx command input and a start input.
Activate the input port and check, if the IN LED lights.
B.9.2 Outputs
Depending upon the programmed criteria, activate the required action using the following table.
Check the contact closure of the programmed outputs on G4AI.
Set the link back to an alarm free operation after this test.
Output on G4AI
Action to enforce the output
Rx command
Inject a Tx command at the corresponding input at the remote
station
Unblocking
Disconnect the RF line coaxial cable
Rx guard
Disconnect the RF line coaxial cable
Ack Tx command
Inject a Tx command at the corresponding input
TPE link alarm
Disconnect the RF line coaxial cable
TPE alarm
Disconnect the RF line coaxial cable
TPE hardware alarm
Inject a Tx command of length > Max. Tx Trip Duration
G4AI alarm
Inject a Tx command of length > Max. Tx Trip Duration
User alarm 1
Depends upon programmed alarm criteria
User alarm 2
Depends upon programmed alarm criteria
Summary of Contents for ETL600
Page 4: ......
Page 32: ......
Page 126: ......
Page 176: ......
Page 206: ......
Page 216: ......
Page 226: ......
Page 264: ......
Page 268: ......
Page 276: ......
Page 284: ......
Page 308: ......
Page 324: ......
Page 346: ......
Page 348: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 380: ......