FCM2000
D184B111U02
6.6.10 Submenu
Alarm
In the following Alarm-Menus the minimum and maximum limits for the variables mass flowrate, density and
temperature can be set. When the value is outside of the maximum or minimum setting, the contact output
can be actuated (additional settings required in the menu Contact Output). The Max-Alarm value must be
larger that the associated Min-Alarm value.
6.6.10.1
Minimum Alarm Mass Flowrate
Set the lower mass flowrate limit. It must be less than the upper mass flowrate limit.
Minimum: 0 %
Maximum: 105 %
6.6.10.2
Maximum Alarm Mass Flowrate
Set the upper mass flowrate limit. It must be greater than the lower mass flowrate limit.
Minimum: 0 %
Maximum: 105 %
6.6.10.3
Minimum Alarm Density
Set the lower density limit. It must be less than the upper density limit.
Minimum: 0.5 g/cm
3
Maximum:
3.5 g/cm
3
Submenu
Alarm
Min Alarm Qm
0.00 %
Max Alarm Qm
100.00 %
Min Alarm
Density 0.5 kg/l
6 Converter
Summary of Contents for CoriolisMaster FCM2000
Page 6: ...Contents 6 FCM2000 D184B111U02...
Page 91: ...11 Certificates D184B111U02 FCM2000 91 Fig 43...
Page 92: ...11 Certificates 92 FCM2000 D184B111U02 11 2 EU Type Examination Certificate Fig 44...
Page 93: ...11 Certificates D184B111U02 FCM2000 93 Fig 45...
Page 94: ...11 Certificates 94 FCM2000 D184B111U02 Fig 46...
Page 95: ...11 Certificates D184B111U02 FCM2000 95 Fig 47...
Page 96: ...11 Certificates 96 FCM2000 D184B111U02 Fig 48...
Page 97: ...11 Certificates D184B111U02 FCM2000 97 Fig 49...
Page 98: ...11 Certificates 98 FCM2000 D184B111U02 Fig 50...
Page 99: ...11 Certificates D184B111U02 FCM2000 99 Fig 51...
Page 100: ...11 Certificates 100 FCM2000 D184B111U02 11 3 PED Certificate of Compliance Fig 52...
Page 101: ...11 Certificates D184B111U02 FCM2000 101 11 4 EHEDG Certificate Fig 53...
Page 103: ......