conductor shall be determined in a manner which produces a conductance equivalent to
that which results from the application of this table.
Minimum cross-sectional area of the corresponding
protective conductor
S
p
(mm
2
)
Cross-sectional area of the phase conductors
S (mm
2
)
S
S ≤ 16
16
16 < S ≤ 35
S/2
35 < S ≤ 400
200
400 < S ≤ 800
S/4
800 < S
Compared to a four-conductor system, the use of symmetrical shielded cable reduces
electromagnetic emission of the whole converter system as well as generator bearing
currents and wear.
The generator cable and its PE pigtail (twisted screen) should be kept as short as possible
in order to reduce electromagnetic emission as well as capacitive current.
■
Typical power cable sizes
CE cables
Generator cables
Total quantity of parallel conductors per phase
Conductor type
Cable type
Converter type
ACS880-77CC-
185 mm
2
240 mm
2
300 mm
2
2×10
2×9
2×6
Copper
EPR
6880A/5500A-7
Grid cables
Total quantity of parallel conductors per phase
Conductor type
Cable type
Converter type
ACS880-77CC-
185 mm
2
240 mm
2
300 mm
2
2×7
2×6
2×5
Copper
EPR
6880A/5500A-7
DC resistor cables
Number of conductor pairs per DC chopper module
Conductor
type
Cable type
Converter type
ACS880-77CC-
35 mm
2
2×1
Copper
EPR
6880A/5500A-7
UL cables
Generator cables
Total quantity of parallel conductors per phase
Conductor
type
Cable type
Converter type
ACS880-77CC-
350 kcmil
400 kcmil
500 kcmil
1000 kcmil
2×17
2×15
2×14
2×10
Copper
EPR
6880A/5500A-7
Grid cables
Total quantity of parallel conductors per phase
Conductor
type
Cable type
Converter type
ACS880-77CC-
350 kcmil
400 kcmil
500 kcmil
1000 kcmil
2×15
2×14
2×13
2×9
Copper
EPR
6880A/5500A-7
52 Planning the electrical installation
Summary of Contents for ACS880-77CC
Page 1: ...ABB WIND TURBINE CONVERTERS ACS880 77CC wind turbine converters Hardware manual...
Page 2: ......
Page 4: ......
Page 10: ...10...
Page 17: ...5 1 3 4 6 8 7 2 Safety instructions 17...
Page 22: ...22...
Page 40: ...40...
Page 60: ...60...
Page 73: ...2a 3b 4c 5 Air flow direction is towards the converter module Maintenance 73...
Page 104: ...104...
Page 108: ...Description CAN bus connection XCAN XCAN 108 BCU x5 control unit...
Page 112: ...112 Dimension drawings...
Page 113: ...Dimension drawings 113...
Page 114: ...114 Dimension drawings...
Page 126: ...126...