Relay cable
The cable type with braided metallic screen (for example, ÖLFLEX from Lapp Kabel,
Germany) has been tested and approved by ABB.
Routing the cables
Route the generator cable away from other cable routes. It is recommended that the generator
cable, grid cable and control cables are installed on separate trays. Avoid long parallel runs
of generator cables with other cables in order to decrease electromagnetic interference
caused by the rapid changes in the converter output voltage.
Where control cables must cross power cables make sure they are arranged at an angle
as near to 90° as possible. Do not run extra cables through the converter.
The cable trays must have good electrical bonding to each other and to the grounding
electrodes. You can use aluminum tray systems to improve local equalizing of potential.
A diagram of the cable routing is below.
90°
min. 500 mm (20 in)
min. 200 mm (8 in)
min. 300 mm (12 in)
1
2
3
4
4
5
Converter
1
Grid cable
2
Control cables
3
Generator cable
4
Power cable
5
56 Planning the electrical installation
Summary of Contents for ACS880-77CC
Page 1: ...ABB WIND TURBINE CONVERTERS ACS880 77CC wind turbine converters Hardware manual...
Page 2: ......
Page 4: ......
Page 10: ...10...
Page 17: ...5 1 3 4 6 8 7 2 Safety instructions 17...
Page 22: ...22...
Page 40: ...40...
Page 60: ...60...
Page 73: ...2a 3b 4c 5 Air flow direction is towards the converter module Maintenance 73...
Page 104: ...104...
Page 108: ...Description CAN bus connection XCAN XCAN 108 BCU x5 control unit...
Page 112: ...112 Dimension drawings...
Page 113: ...Dimension drawings 113...
Page 114: ...114 Dimension drawings...
Page 126: ...126...