Fuses
■
Main circuit AC fuses
AC fuses
Converter type
ACS880-77CC-
Qty
I
N
A rms
Type
U
N
= 690 V
2×12
1250
170M6416
6880A/5500A-7
3AXD10000011539
■
Main circuit DC fuses
DC fuses
Converter type
ACS880-77CC-
Qty
I
N
A rms
Type
U
N
= 690 V
2×8
1400
170M6151
6880A/5500A-7
3AXD10000011539
■
Fuses for the voltage measurement board BAMU
The fuse type is Mersen FR14GR69V2T, 2 A.
■
Fuses of the DC chopper
The fuse type is 170M4243 (>1000 V).
Dimensions, weights and free space requirements
See also chapter
.
Weight
Dimensions
Converter type
ACS880-77CC-
Width
Depth
Height
kg (lb)
mm (in)
mm (in)
mm (in)
U
N
= 690 V
3300 (7275)
4125 (162.4)
600 (23.6)
2299 (90.5)
6880A/5500A-7
3AXD10000011539
For free space requirements, see the dimension drawings.
Technical data 89