100
ACS510 User’s Manual
Start-Up
2611
USER F1
Frequency(in Hz), at which output voltage reference is P2610 USER U1.
Please see parmeter 2605.
2612
USER U2
This parameter define the output voltage reference (in Volts) at P2613 USER F2.
Please see parmeter 2605.
2613
USER F2
Frequency(in Hz), at which output voltage reference is P2612 USER U2.
Please see parmeter 2605.
2614
USER U3
This parameter define the output voltage reference (in Volts) at P2615 USER F3.
Please see parmeter 2605.
2615
USER F3
Frequency(in Hz), at which output voltage reference is P2614 USER U3.
Please see parmeter 2605.
2616
USER U4
This parameter define the output voltage reference (in Volts) at P2617 USER F4.
Please see parmeter 2605.
2617
USER F4
Frequency(in Hz), at which output voltage reference is P2616 USER U4.
Please see parmeter 2605.
2618
FW VOLTAGE
Maximum output voltage of drive when the output frequency is controlled to level defined by parameter P9907
MOTOR NOM FREQ
.
Please see parmeter 2605.
NOTE!
• The actual output voltage reference is the lower value of the values of parameters P9905 MOTOR NOM VOLT and
P2618 FW VOLTAGE.
• Requirements for parameters setting: P2618>P2616>P2614>P2612>P2610 and
P9907>P2617>P2615>P2613>P2611. If this not true, FAULT 1015 (
PAR
USER
DEFINED
U
/
F
) is generated (only
when P2605 u/f
RATIO
= 3).
2619
DC STABILIZER
Enables or disables the DC voltage stabilizer. The DC stabilizer is used in scalar control mode to prevent possible
voltage oscillations in the drive DC bus caused by motor load or weak supply network. In case of voltage variation the
drive tunes the frequency reference to stabilize the DC bus voltage and therefore the load torque oscillation.
0 =
DISABLE
– Disables DC stabilizer.
1 =
ENABLE
– Enables DC stabilizer.