ACS510 User’s Manual
231
Technical Data
-05A6-4
R1
73
249
44
26
-07A2-4
R1
97
331
44
26
-09A4-4
R1
127
434
44
26
-012A-4
R1
172
587
44
26
-017A-4
R2
232
792
88
52
-025A-4
R2
337
1151
88
52
-031A-4
R3
457
1561
134
79
-038A-4
R3
562
1919
134
79
-046A-4
R3
667
2278
134
79
-060A-4
R4
907
3096
280
165
-072A-4
R4
1120
3825
280
165
-088A-4
R4
1440
4918
280
165
-125A-4
R5
1940
6625
350
205
-157A-4
R6
2310
7889
405
238
-180A-4
R6
2810
9597
405
238
-195A-4
R6
3050
10416
405
238
-246A-4
R6
3850
13148
540
318
-290A-4
R6
4550
15539
540
318
Drive
Heat Loss
Air Flow
ACS510-01-
Frame Size
W
BTU/hr
m
3
/h
ft
3
/min
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd