ACS510 User’s Manual
167
Embedded Fieldbus
ABB Drives Profile
The following table and the state diagram later in this sub-section describe the
STATUS
WORD
content for the ABB Drives profile.
ABB Drives Profile (EFB)
STATUS
WORD
(See Parameter 5320)
Bit
Name
Value
Description
(Correspond to states/boxes in the state diagram)
0
RDY_ON
1
READY
TO
SWITCH
ON
0
NOT
READY
TO
SWITCH
ON
1
RDY_RUN
1
READY
TO
OPERATE
0
OFF
1
ACTIVE
2
RDY_REF
1
OPERATION
ENABLED
0
OPERATION
INHIBITED
3
TRIPPED
0…1
FAULT
0
No fault
4
OFF_2_STA
1
OFF
2
INACTIVE
0
OF
F
2
ACTIVE
5
OFF_3_STA
1
OFF
3
INACTIVE
0
OF
F
3
ACTIVE
6
SWC_ON_INHIB
1
SWITCH
-
ON
INHIBIT
ACTIVE
0
SWITCH
-
ON
INHIBIT
NOT
ACTIVE
7
ALARM
1
Warning/alarm (See "Alarm Listing" in the "Diagnostics" section
for details on alarms.)
0
No warning/alarm
8
AT_SETPOINT
1
OPERATING
.
Actual value equals (within tolerance limits) the
reference value.
0
Actual value is outside tolerance limits (not equal to reference
value).
9
REMOTE
1
Drive control location:
REMOTE
(
EXT
1 or
EXT
2)
0
Drive control location:
LOCAL
10
ABOVE_LIMIT
1
Supervised parameter’s value > supervision high limit.
Bit remains “1” until supervised parameter’s value < supervision
low limit.
See group 32, Supervision
0
Supervised parameter’s value < supervision low limit.
Bit remains “0” until supervised parameter’s value > supervision
high limit.
See group 32, Supervision
11
EXT CTRL LOC
1
External control location 2 (
EXT
2) selected
0
External control location 1 (
EXT
1) selected
12
EXT RUN ENABLE 1
External Run Enable signal received
0
No External Run Enable signal received
13…
15
Unused