88
ACS510 User’s Manual
Start-Up
1609
START ENABLE 2
Selects the source of the start enable 2 signal.
Note:
Start enable functionality differs from the run enable functionality.
0 =
NOT
SEL
– Allows the drive to start without an external start enable signal.
1 =
DI
1 – Defines digital input DI1 as the start enable 2 signal.
• This digital input must be activated as the start enable 2 signal.
• If the voltage drops and de-activates this digital input, the drive will coast to stop and show alarm 2022 on panel
display. The drive will not start until start enable 2 signal resumes.
2…6 =
DI
2…
DI
6 – Defines digital input DI2…DI6 as the start enable 2 signal.
• See DI1 above.
7 =
COMM
– Assigns the fieldbus Command Word as the source for the start enable 2 signal. Bit 3 of the Command
word 2 (parameter 0302) activates the start disable 2 signal.
• See fieldbus user’s manual for detailed instructions.
(-1) =
DI
1(
INV
) – Defines an inverted digital input DI1 as the start enable 2 signal.
(-2)…(-6) =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input DI2…DI6 as the start enable 2 signal.
• See
DI
1 (
INV
) above.
1610
DISPLAY ALARMS
Controls the visibility of the following alarms:
• 2001, Overcurrent alarm
• 2002, Overvoltage alarm
• 2003, Undervoltage alarm
• 2009, Device overtemperature alarm
0 =
NO
– The above alarms are suppressed.
1 =
YES
– All of the above alarms are enabled.