ACS510 User’s Manual
119
Start-Up
4016
ACT1 INPUT
Defines the source for actual value 1 (
ACT
1). See also parameter 4018
ACT1 MINIMUM
.
1 =
AI
1 – Uses analog input 1 for
ACT
1.
2 =
AI
2 – Uses analog input 2 for
ACT
1.
3 =
CURRENT
– Uses current for
ACT
1.
4=
TORQUE
– Uses torque for
ACT
1.
5=
POWER
– Uses power for
ACT
1.
6 =
COMM ACT
1 – Uses value of signal 0158
PID COMM VALUE
1 for
ACT
1.
7 =
COMM ACT
2 – Uses value of signal 0159
PID COMM VALUE
2 for
ACT
1.
4017
ACT2 INPUT
Defines the source for actual value 2 (
ACT
2). See also parameter 4020
ACT2 MINIMUM
.
1 =
AI
1 – Uses analog input 1 for
ACT
2.
2 =
AI
2 – Uses analog input 2 for
ACT
2.
3 =
CURRENT
– Uses current for
ACT
2.
4 =
TORQUE
– Uses torque for
ACT
2.
5 =
POWER
– Uses power for
ACT
2.
6 =
COMM ACT
1 – Uses value of signal 0158
PID COMM VALUE
1 for
ACT
2.
7 =
COMM ACT
2 – Uses value of signal 0159
PID COMM VALUE
2 for
ACT
2.
4018
ACT1 MINIMUM
Sets the minimum value for
ACT
1.
• Scales the source signal used as the actual value
ACT
1 (defined
by parameter 4016
ACT
1
INPUT
). For parameter 4016 values
6 (
COMM
ACT
1) and 7 (
COMM
ACT
2) scaling is not done.
• See the figure: A= Normal; B = Inversion (
ACT
1
MINIMUM
>
ACT
1
MAXIMUM
)
4019
ACT1 MAXIMUM
Sets the maximum value for
ACT
1.
See 4018
ACT
1
MINIMUM
.
4020
ACT2 MINIMUM
Sets the minimum value for
ACT
2.
See 4018
ACT
1
MINIMUM
.
4021
ACT2 MAXIMUM
Sets the maximum value for
ACT
2.
See 4018
ACT
1
MINIMUM
.
4022
SLEEP SELECTION
Defines the control for the PID sleep function.
0 =
NOT
SEL
– Disables the PID sleep control function.
1 =
DI
1 – Defines digital input
DI
1 as the control for the PID sleep function.
• Activating the digital input activates the sleep function.
• De-activating the digital input restores PID control.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for the PID sleep function.
• See
DI
1 above.
7 =
INTERNAL
– Defines the output frequency, process reference, and process actual value as the control for the PID
sleep function. Refer to parameters 4025
WAKE
-
UP
DEV
and 4023
PID
SLEEP
LEVEL
.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the control for the PID sleep function.
• De-activating the digital input activates the sleep function.
• Activating the digital input restores PID control.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the control for the PID sleep function.
• See
DI
1(
INV
) above.
Code Description
Par 4016
Source
Source min.
Source max.
1
Analog input 1 1301
MINIMUM
AI
1
1302
MAXIMUM
AI
1
2
Analog input 2 1304
MINIMUM
AI
2
1305
MAXIMUM
AI
2
3
Current
0
2 · nominal current
4
Torque
-2 · nominal torque 2 · nominal torque
5
Power
-2 · nominal power 2 · nominal power
Source signal
P 4019
P 4018
Source min
Source max
Source min
Source max
P 4018
P 4019
ACT
1 (%)
Source signal
ACT
1 (%)
A
B
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: [email protected]