ACS510 User’s Manual
Start-Up
Group 01: Operating Data
This group contains drive operating data, including actual signals. The drive sets the
values for actual signals, based on measurements or calculations. You cannot set
these values.
Code Description
0101
SPEED & DIR
The calculated signed speed of the motor (rpm). The absolute value of this parameter is the same as the value of
0102
SPEED
.
• The value is positive if the moter runs in the forward direction.
• The value is negative if the moter runs in the reverse direction.
0102
SPEED
The calculated speed of the motor (rpm).
0103
OUTPUT FREQ
The frequency (Hz) applied to the motor. (Shown by default in the control panel OUTPUT mode.)
0104
CURRENT
The motor current, as measured by the ACS510. (Shown by default in the control panel OUTPUT mode.)
0105
TORQUE
Output torque. Calculated value of torque on motor shaft in % of motor nominal torque. (Shown by default in the
control panel OUTPUT mode.)
0106
POWER
The measured motor power in kW.
0107
DC BUS VOLTAGE
The DC bus voltage in V DC, as measured by the ACS510.
0109
OUTPUT VOLTAGE
The voltage applied to the motor.
0110
DRIVE TEMP
The temperature of the drive power transistors in degree Celsius.
0111
EXTERNAL REF 1
External reference,
REF
1, in Hz.
0112
EXTERNAL REF 2
External reference,
REF
2, in %.
0113
CTRL LOCATION
Active control location. Alternatives are:
0 =
LOCAL
1 =
EXT
1
2 =
EXT
2
0114
RUN TIME (R)
The drive’s accumulated running time in hours (h).
Can be
reset
by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0115
KWH COUNTER (R)
The drive’s accumulated power consumption in kilowatt hours.
Can be
reset
by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0116
APPL BLK OUTPUT
Application block output signal. Value is from either:
• PFC control, if PFC Control is active, or
• Parameter 0112
EXTERNAL
REF
2.