Commissioning
System Manual
│79
Operating mode
If an outdoor station is to be set up or added for a perimeter (e.g. park house), it is
commissioned as normal, just like every other outdoor station.
The outdoor station operation for the perimeter is different only in the operating mode and the
physical address.
Perform the following points for commissioning or adding the outdoor station for the perimeter:
■
Start the operation of the outdoor station as normal, see chapter 6.2.5 “Outdoor station with
push-buttons“ on page 77.
– Perform the following deviations at the same time:
Fig. 54: Outdoor station with buttons: Set the operating mode via the indoor station
1. At the indoor station set the operating mode for the outdoor station on "Gate station".
■
GS: Gate station (Gate Station)
■
OS: Outdoor station (Outdoor Station)
2. Set the physical address for a gate station. A gate station only has the physical address of
the device, see chapter 6.2.1 “Fundamentals of physical addressing ABB-Welcome IP“ on
page 63.
– Address range: 01 - 32