Fan level manual control 3
Manual fan
1 bit EIS1 DPT 1.001
C,R,W,T
This 1-bit communication object can be used to send an ON telegram, if the second fan stage
to be switched on. An OFF telegram is sent, if the third fan stage is no longer to be switched on.
This data item forms the 1-bit KNX object and can be sent and received.
36
Speed 1 automatic control
Automatic fan
1 bit EIS1 DPT 1.003
C,R,W,T,U
This 1-bit communication object can be used by the ambient temperature controller to receive
information about the status of the fan coil actuator. It can evaluate whether stage 1 or no
stage was activated.
37
Speed 2 automatic control
Automatic fan
1 bit EIS1 DPT 1.003
C,R,W,T,U
This 1-bit communication object can be used by the ambient temperature controller to receive
information about the status of the fan coil actuator. It can evaluate whether stage 1 or no
stage was activated.
38
Speed 3 automatic control
Automatic fan
1 bit EIS1 DPT 1.003
C,R,W,T,U
This 1-bit communication object can be used by the ambient temperature controller to receive
information about the status of the fan coil actuator. It can evaluate whether stage 1 or no
stage was activated.
6.3.5 Remote thermostats
No.
Function
Object name
Type of datum
Flags
39,40,
41
Remote mode 1,2,3
Remote
thermostats
1 byte EIS1 DPT
20.102
C,R,T
It sends the set operating mode of the Programmable Thermostat to the possible three remote thermostats. The
possible values are:
0: Programmable Thermostat mode
1: Programmable Thermostat setpoint only
2: Se comfort mode
42,43,
44
Remote setpoint 1,2,3
Remote
thermostats
2 byte EIS1 DPT 9.001
C,R,T
It sends the setpoint temperature value of the Programmable Thermostat to the remote thermostats.