Commissioning 43
MYLOS
®
Building Automation
Commissioning
6.1.12 Parameter window “FanCoil heating”
Step limit in night mode
Options:
-
No limit
- Fan Off
- Level 1
- Level 2
If the device is used in an environment such as a hotel room, it may be desirable to limit the fan stages during the
night to reduce the noise.
The parameter “Stage limit in night mode” is used for this. If the parameter is set to stage 1, the fan will not use
more that the first stage when night mode is enabled. This will apply even if the transmitted control value requests
a higher fan stage.
Automatic return from manual adjustment (0 - inactive, min)
Options:
-
0
- 1
- 2
- …
- 60
If “Manual stage switching” was performed by the user, this action can be reset via onsite operation of the ambient
temperature controller.
However, a time can also be input after which the ambient temperature cancels the “Manual stage switching” and
switches back to automatic stage switching mode.
This parameter is only available if the “Heating” or “Heat and cool” control functions are used and the heating control
type is set to “FanCoil”.