6.1.10 Parameter window “Setpoint heat/cool”
Heating setpoint comfort mode
Options:
- 16.0 °C
- 16.5 °C
- …
-
21.0 °C
- …
- 31.0 °C
The “Heating setpoint comfort mode” specifies the individual comfort temperature for the heating mode. This
parameter is only available if the “Heating” or “Heat and cool” control functions are used, in which the setpoints
“Dependent setpoints” (tab “Setpoints general”) have been selected and the reference of the base setpoint has been
set to “Base setpoint heating”.
Heating setpoint reduction standby
Options:
- 0.5 K
- 1.0 K
- …
-
2 K
- …
- 8.0 K
The setting “Heating setpoint reduction standby” allows you to specify the number of degrees Kelvin that the comfort
temperature is lowered during standby operation.
This parameter is only available if the parameter “Selection of base setpoint” (tab “Setpoint general”) is set to
“Dependent setpoints”.