Commissioning
6.1.9 Parameter window “Manual setpoint”
Manual setpoint adjustment
Options:
- Disabled
-
Active
This parameter allows end users to adjust the configured setpoint during commissioning. The settings “... manual
increase and reduction of the setpoint” is used to specify how high or low the setpoint can be moved. The value that
is parametrised for manually configuring the setpoint is an amount that fluctuates around the setpoint.
Example: with a comfort temperature of 21 °C and a manual setpoint adjustment of +/- 3 K, users can select any
temperature from 18 °C to 24 °C.
Maximum manual setpoint increase
Options:
- 0 K
- 1 K
- 2 K
-
3 K
- 4 K
- 5 K
- 6 K
- 7 K
- 8 K
- 9 K
- 10 K
If you wish to prevent an excessive temperature increase by the manual setpoint setting, the upper range of the
manual setpoint preset can be limited with the parameter “Maximum manual setpoint increase”.
Example: with a comfort heating temperature of 21 °C and a manual setpoint adjustment of +/- 3 K, users can select
any temperature from 18 °C to 24 °C. If the comfort temperature can be increased to a maximum of 22 °C, enter “1
K” under the parameter “Max. increase of setpoint”.