22 Commissioning
| MYLOS
®
Building Automation
MYLOS
®
Building Automation
Commissioning
6.1.2 Parameter window: “Temperature measurement”
Offset for room temp. meas. (measured value changed by (-128..127)x0,1 K)
Options:
- -30
- …
-
0
- …
- 30
Temperature range -30..30 corresponds to –3K..3K
If the actual temperature is recorded internally, it may be falsified by an additional internal heat source, e.g. bus
or network coupler. The falsified value can be adjusted with the setting “calibration value for ambient temperature
measurement”.
Setpoint larger when sending change
Options:
-
Inactive
- 0.1 K
- 0.2 K
- 0.3 K
- 0.4 K
- 0.5 K
- 0.6 K
- 0.7 K
- 0.8 K
- 0.9 K
- 1.0 K
If this parameter is set to a difference, the associated 2-byte communication object “Current temperature” sends its
current temperature whenever this parameter changes.