Annual Service
In addition to the above the following should be carried out:
• Open the front cover of the Main control panel.
• Remove one leg of the fire alarm and the curtain or curtains should deploy and
close to their correct position without any snagging .
• Inspect the curtain for any visual damage pay particular attention to the bottom
bar.
• Remove the guide fronts and inspect the curtain retainer system, check the
smoke seals condition if installed.
• Check the guide to structure fixings are secure.
• Refit the guide front.
• Remove the box housing front and inspect the security bolts on either end of
the roller assembly.
• Check the curtain to roller fixing are secure.
• Check the motor cable for damage.
• Replace the box housing front
• Check the operation of any emergency retract switches if installed.
• Check the function of any auxiliary devices.
• Refit the alarm signal leg.
• The curtain should safely retract to the open position
• Check the voltage of the batteries this should be greater than 24 volts. The
voltage is displayed on the LCD display screen or a multimeter should be used.
This should be carried out by fully trained fire/smoke curtain
engineers.
69
Summary of Contents for Evo1-MCP 1
Page 4: ...Back to contents Mechanical Installation Instructions 4...
Page 17: ...Back to contents Control Panel Lighting 17...
Page 20: ...Back to contents Motor Control Board Lighting 20...
Page 22: ...Back to contents General Overview Instructions 22...
Page 25: ...Back to contents Control Panel Wiring 25...
Page 30: ...Back to contents Motor Control Board Wiring 30...
Page 36: ...Back to contents Dip Switch Settings 36...
Page 39: ...Back to contents Override Switch Wiring to Control Panel 39...
Page 41: ...Back to contents Override Switch Wiring to Motor Control Board 41...
Page 44: ...Back to contents Control Panel Function Programming 44...
Page 54: ...Back to contents Optional Extras 54...
Page 58: ...Wiring of Optional Extras 58...
Page 64: ...Back to contents Fault Finding 64...
Page 67: ...Back to contents Maintenance Service 67...
Page 74: ...Back to contents Standard Drawings Headbox and Guides 74...
Page 84: ...Back to contents 44 0 1204 383839 info a1shutters co uk www a1sgroup com...