• CPM red light on indicates there is a system malfunction on the
panel programming, wiring or PCB failure.
• Delay blue light indicates there is an active alarm signal been
received and the panel is holding the curtains for the programmed
time in the stored settings.
• A Green light Power on indicates the panel has a healthy mains
supply to the PSU.
• Amber light Low battery fault on indicates either there is a mains
failure to the panel or the batteries are below the required
voltage and will require charging, the panel constantly monitors
the battery voltage and will detect when low, once recharged the
light will go out.
If the light does not go out after 2 hours the batteries will require
replacing. If the panel has had no mains supply the batteries will
hold the curtains in the retracted position until the low voltage
close system has been triggered, the curtains will then close in a
controlled decent but will no longer retract until the mains supply
is reinstated. If the batteries have totally depleted the LCD
screen will be blank and both batteries will require replacement.
• Alarm red light on indicates there is an active signal to one of the
panel inputs, this could be the main alarm terminal or either input
1 or input 2, this will not go off until the signal has returned to
normally closed.
• Override amber light on indicates there is an active signal to
one of the panel inputs, this could be the main alarm terminal
or either input 1 or input 2 and the override button has been
pressed, once the curtain has returned to its fire safe position
the light will go out.
19
Summary of Contents for Evo1-MCP 1
Page 4: ...Back to contents Mechanical Installation Instructions 4...
Page 17: ...Back to contents Control Panel Lighting 17...
Page 20: ...Back to contents Motor Control Board Lighting 20...
Page 22: ...Back to contents General Overview Instructions 22...
Page 25: ...Back to contents Control Panel Wiring 25...
Page 30: ...Back to contents Motor Control Board Wiring 30...
Page 36: ...Back to contents Dip Switch Settings 36...
Page 39: ...Back to contents Override Switch Wiring to Control Panel 39...
Page 41: ...Back to contents Override Switch Wiring to Motor Control Board 41...
Page 44: ...Back to contents Control Panel Function Programming 44...
Page 54: ...Back to contents Optional Extras 54...
Page 58: ...Wiring of Optional Extras 58...
Page 64: ...Back to contents Fault Finding 64...
Page 67: ...Back to contents Maintenance Service 67...
Page 74: ...Back to contents Standard Drawings Headbox and Guides 74...
Page 84: ...Back to contents 44 0 1204 383839 info a1shutters co uk www a1sgroup com...