2 core fire rated cable is required
Wiring of additional remote test
key switches
Wiring of remote test key switch to
the main control panel Input 1 or 2
IN1 Brown
OV Blue
Use only the yellow pair of wires normally
open.
Brown to Yellow
Blue to Yellow
OFF = Stand by
ON = Test
The key can be removed in either position.
Wiring of remote test key switch
to the key switch
Key Positions
Either input 1 (IN1) or 2 (IN2) can be configured
• Press right hand button on the control panel for 2 seconds to enter
programming mode, scroll by continually pressing until “spare input 1”
• Press the middle button to “fire alarm”
• Once set store by pressing the right button for 2 seconds “Save changes”
on LCD screen press middle button until “yes” Press the right button
for 2 seconds the screen returns to “Flameshield Evo 1” and is now out of
programming mode and in standby.
Summary of Contents for Evo1-MCP 1
Page 4: ...Back to contents Mechanical Installation Instructions 4...
Page 17: ...Back to contents Control Panel Lighting 17...
Page 20: ...Back to contents Motor Control Board Lighting 20...
Page 22: ...Back to contents General Overview Instructions 22...
Page 25: ...Back to contents Control Panel Wiring 25...
Page 30: ...Back to contents Motor Control Board Wiring 30...
Page 36: ...Back to contents Dip Switch Settings 36...
Page 39: ...Back to contents Override Switch Wiring to Control Panel 39...
Page 41: ...Back to contents Override Switch Wiring to Motor Control Board 41...
Page 44: ...Back to contents Control Panel Function Programming 44...
Page 54: ...Back to contents Optional Extras 54...
Page 58: ...Wiring of Optional Extras 58...
Page 64: ...Back to contents Fault Finding 64...
Page 67: ...Back to contents Maintenance Service 67...
Page 74: ...Back to contents Standard Drawings Headbox and Guides 74...
Page 84: ...Back to contents 44 0 1204 383839 info a1shutters co uk www a1sgroup com...