SB1: Stop button; SB2: Run forward button; SB3: Run reverse button
Terminal Xi is the multi-function input terminal of X1~X5. For this case,
the corresponding parameter should be set at 16 ( 3-wire operation ) .
3: 3-wire operating mode 2
Running
direction
K
FWD
0
REV
1
P24
Xi(REV)
COM
Xi
PLC
Xi(FWD)
SB2
SB1
K
Figure 7-11 3-Wire Operation Mode 2
SB1: Stop button; SB2: Run button
Terminal Xi is the multi-function input terminal of X1~X5. For this case,
the corresponding parameter should be set at 16 ( 3-wire operation ) .
Table 7-6
P5.09~P5.11Reserved
Reserved
P5.12 Filter constant
Range: 0.01
~
50.00s
【
0.50s
】
P5.13 Reserved
Reserved
P5.14 Ratio of Min. input of curve 1
Range: 0.0
%~
P5.16
【
2.0
%】
P5.15 Frequency corresponds to min. input
of curve 1
Range: 0.0
~
P0.09
【
0.00Hz
】
P5.16 Ratio of Max. input of curve1
Range: P5.14
~
100.0
%【
100.0
%】
P5.17 Frequency corresponds to max.
input of curve 1
Range: 0.0
~
P0.09
【
50.00Hz
】
P5.18~P5.21Reserved
Reserved
7.7 Output terminal control parameters ( P6 )
Table 7-7
P6.00 Open collector output terminal Y1
Range: 0
~
19
【
0
】
P6.01 Reserved
Reserved
P6.02 Relay 1 output function
Range: 0
~
19
【
16
】