Baud rate:
0
:
1200BPS
1
:
2400BPS
2
:
4800BPS
3
:
9600BPS
4
:
19200BPS
5
:
38400BPS
Data format
0
:
1 - 8 - 2
format
,
No parity
,
RTU
1
:
1 - 8 - 1
Format, Evenparity ,RTU
2
:
1 - 8 - 1
Format ,Odd parity ,RTU
,
Fictitious input terminal
0
:
Disabled
1
:
Enabled
Figure 7-22 Communication Configuration
This function code according to LED mode, used for serial
communication preferences. Note: Controller with frequency conversion
to set the baud rate and data format must agree, otherwise, the
communication can't be.
Virtual terminal is refers to the controller sends commands are adopted to
simulate the actual terminal, with each representing a data terminal, each
value represents the corresponding terminal state: bit0 ~ bit12: virtual
terminal X1 and X5, NC, NC, NC, NC, Y1, NC, TC, NC.PC virtual terminal
is valid, the actual terminal function is invalid, virtual terminal equivalent
terminal application.
In serial communication, PB.01 is unique, used to identify the inverter
address.
Note: “0” is the broadcast address. When the address is set to broadcast
address, the inverter can receive and execute the command sent by
control FC, but will not answer it.
When the communication signal is lost for a period longer than the setting
of this parameter, the inverter deems that communication fault occurs.
When it is set at 0, the inverter will not detect the signals at the serial port,
i.e., this function is invalid.
PB.01 Local address
Range: 0
~
247
【
1
】
PB.02 Communicate timeout detect
Range: 0
~
1000.0s
【
0.0s
】
PB.03 Response delay
Range: 0
~
1000ms
【
5ms
】