5.2 Wiring
5.2.1 Overview
Please finish the power circuit and control circuit wiring.
The figure below is the systematic wiring of the inverter.
PB ( -)
R
S
T
R
S
T
3-phase
380 V
50/ 60 Hz
M
U
V
W
PE
Auxiliary
power
Circuit
breake
DC current meter
0/4~20mA current
signal
AO
COM
GND
1TB
1TC
1TA
Programmable relay output
RS485 -
RS485+
Standard RS485
communication port
X 1
X 2
X 3
X 4
X 5
Multi-function input 1
PLC
COM
Speed
command
GND
+ 10 V
PE
0
~
10V/ 0
~
20 mA
Y 1
Output 1:
Open collector signal
P24
I
V
CN6
0 / 2
~
10V
.
.
.
0 / 4
~
20 mA
CN4
(+)
Power
circuit
Control
ciruit
P 24
ON
OFF
CN 5
.
.
.
.
.
.
Multi-function input 2
Multi-function input 3
Multi-function input 4
Multi-function input 5
AI
DT100
Figure 5-2 Systematic Wiring Diagram
Table 5-1 Recommended MCCB Capacity and Copper Cable Section
Area
Model
MCCB
Circuit
breaker
( A )
Power circuit ( mm
2
)
Control
cable
( mm
2
)
Input
cable
Braking
line
Output
cable
Earth
cable
DT100-0001-2S
16
1.5
1.0
1.0
2.5
1.0
DT100-0002-2S
20
2.5
1.0
1.0
2.5
1.0
DT100-0003-2S
32
4.0
1.5
2.5
4.0
1.0
DT100-0004-2S
50
6.0
1.5
2.5
6.0
1.0
DT100-0002-4T
10
1.0
1.0
1.0
2.5
1.0
DT100-0003-4T
16
1.5
1.0
1.5
2.5
1.0
DT100-0004-4T
16
1.5
1.5
1.5
2.5
1.0