Control mode
ON
OFF
Terminal
ON
ON
Serial port
The selection of control mode is realized by the combination of ON/OFF
state of any two of X1~X5. In the above table, you should set P5.00=28,
P5.01=29.
30~34: Reserved
35: External Stop command
This Stop command is valid to all control modes. When this function is
enabled, the inverter will stop as specified P2.08.
36: Reserved
37: Prohibit inverter from operating
If this function is enabled, the inverter that is operating will coast to stop
and the inverter ready to run will be prohibited to start. This function is
mainly used as safety protection.
38: Reserved
39: Reserved
40: Clear the setting of auxiliary reference frequency
This function is valid for auxiliary reference frequency ( P0.03=1, 2 and
3 ) to clear it to zero, so that the reference frequency is determined
solely by main reference.
41: Reset PLC state
When the inverter stops in PLC mode, the memorized PLC operating
information ( operating stage, operating time, operating frequency, etc. )
will be cleared.
42: Clear the counter to zero
This function is to clear the counter to zero and is used in conjunction with
function 43.
43: Input signal to trigger the counter