Display
(fl ashing) Info
Error/warning
Possible cause
Remedy
F15
Message appears after
a start command.
Error when testing
CLOSE closing edge
protection.
CLOSE closing edge protection was
active during testing.
Check connection and function of closing
edge protection and associated evaluation
device.
Closing edge protection was activated,
but no closing edge protection is
connected.
Deactivate closing edge protection in menu
P34
. See
Page 24
.
Incorrect evaluation type set.
Set correct evaluation type in menu
P35
.
See
"Evaluation of the closing edge
protection" on page 25
.
The closing edge protection input has
been short-circuited with a wire jumper.
Remove wire jumper, connect closing edge
protection and corresponding evaluation
device or deactivate closing edge protection
in menu
P34
if not present.
F20
Message appears after
a start command in
open direction or during
opening.
Force shutdown during
gate opening
The gate is running sluggishly/unevenly
Correct gate run, teach in opener again if
necessary or adjust value in menu
P39.o
or
P40.o
.
There is an obstacle in the gate area
Remove obstacle.
F26
Message appears after
a start command in
close direction or during
closing.
Force shutdown during
gate closing
The gate is running sluggishly/unevenly
Correct gate run, teach in opener again if
necessary or adjust value in menu
P39.c
or
P40.c
.
There is an obstacle in the gate area
Remove obstacle.
F27
Message appears after
a start command in
close direction or during
closing.
5x force shutdown or
closing edge protection
in succession during
gate closing.
(Error indicator only
appears if automatic
gate closing is selected).
The gate is running sluggishly/unevenly
Correct gate run, teach in opener again if
necessary or adjust value in menu
P39.c
or
P40.c
.
There is an obstacle in the gate area
Remove obstacle.
The closing edge protection is defective
Check the closing edge protection and
replace if necessary. The opener must be
restarted by a command.
Note:
The automatic gate closing function is locked and must be restarted by a start command.
F31
Message appears after
a start command or
when gate moving.
Light barrier type 1 was
active.
Light barrier at terminals J5 and J9
was interrupted or actuated, see
"7.24
Photocell 1 input (terminals J5/J9)" on
page 24
.
Remove obstacle which triggered the light
barrier and/or check and replace the light
barrier if necessary.
When no light barrier is connected, menu
P30
must be set to
AUS
.
F32
Message appears after
a start command in
open direction or during
opening.
OPEN closing edge
protection was active.
Closing edge protection at terminals
J7 and J9 was interrupted or actuated,
see
"7.27 Closing edge protection
1 (terminals J7/J9) input" on page
24
.
Remove obstacle which triggered the
closing edge protection and/or check and
replace the closing edge protection/supply
line if necessary.
When no closing edge protection is
connected, menu
P33
must be set to
nEin
.
Incorrect evaluation activated, see
"7.29 Evaluation of the closing edge
protection" on page 25
.
Set correct evaluation in menu
P35
.
F33
Message appears after
a start command.
Error when testing
OPEN closing edge
protection.
OPEN closing edge protection was active
during testing.
Check connection and function of closing
edge protection and associated evaluation
device.
Closing edge protection was activated,
but no closing edge protection is
connected.
Deactivate closing edge protection in menu
P33
. See
Page 24
.
Incorrect evaluation type set.
Set correct evaluation type in menu
P35
.
See
"Evaluation of the closing edge
protection" on page 25
.
The closing edge protection input has
been short-circuited with a wire jumper.
Remove wire jumper, connect closing edge
protection and corresponding evaluation
device or deactivate closing edge protection
in menu
P33
if not present.
F37
Message appears after
a start command.
Error when testing light
barrier type 1
Light barrier was active during testing.
Check light barrier or supply line to light
barrier and replace if necessary.
Remove obstacle.
A light barrier was activated, but no light
barrier is connected.
Deactivate light barrier in menu
P30
. See
Page 24
.
The light barrier input has been short-
circuited with a wire jumper.
Remove wire jumper and deactivate light
barrier in menu
P30
. See
Page 24
.
F38
Message appears after
a start command.
Error when testing light
barrier type 2
Light barrier was active during testing.
Check light barrier or supply line to light
barrier and replace if necessary.
Remove obstacle.
A light barrier was activated, but no light
barrier is connected.
Deactivate light barrier in menu
P31
. See
Page 24
.
The light barrier input has been short-
circuited with a wire jumper.
Remove wire jumper and deactivate light
barrier in menu
P31
. See
Page 24
.