ENGLISH
13
5
COMMISSIONING/CONNECTING
ADDITIONAL COMPONENTS
5.1
Information on electrical work
DANGER!
Power supply
Contact with the power supply poses a risk of fatal electric
shock.
Always observe the following information:
►
Electrical connections may only be established by a qualifi ed
electrician.
►
The on-site electrical installation must comply with the
respective safety regulations (230/240 V AC, 50/60 Hz).
►
Before commencing electrical work, ensure that the system
is fully de-energised and secure it against unauthorised re-
activation.
ATTENTION!
•
Applying external voltage to the connection terminals of the
control system will destroy the electronics!
•
To avoid malfunctions, ensure that the control lines of the
opener (24 V DC) are laid in an installation system separate
from the other supply lines (230 V AC)!
WARNING!
Risk of injury from
unintentional gate movement!
In the event of improper
installation or operation of the
opener, unintentional gate
movements may be triggered
which may cause people or
objects to become trapped.
In the event of improperly attached control units (e.g. buttons),
unintentional gate movements may be triggered which may
cause people or objects to become trapped.
►
Follow all instructions contained in this manual.
►
Attach control units at a height of minimum 1.5 m (outside of
the reach of children).
►
Install fi xed control units (e.g. buttons) within sight of the
gate but away from moving parts.
In the event of the failure of safety devices, persons or objects
may become trapped.
►
In accordance with ASR 1.7, install at least one easily
identifi able and accessible emergency command device
(emergency stop) in the vicinity of the gate, which may be
used to stop the gate in the event of danger.
5.2
Electrical connection of the opener
The mains connection (230 V AC/50 Hz) of the opener requires
a line NYY 3 x 1.5 mm
2
(to 20 m supply line) or NYY 3 x 2.5 mm
2
(to 30 m supply line). The supply line must be secured with an
ELCB (30 mA) in accordance with the statutory requirements.
In accordance with ASR 1.7, an all-pole-disconnecting lockable
main switch must be installed in the area of the opener between
the mains supply line and the supply line to the opener.
Connect the supply line to terminals
L
and
N
on the power board
and the protective conductor
PE
to the protective conductor
connection of the opener housing.
See
"Figure 13 - Opener mains connection"
.
50-60 Hz
230Vac
L
N
MAINS
13
Figure 13 - Opener mains connection
Note
The remaining accessories may only be connected following
a complete test run in conjunction with the motor control,
command unit and correct limit switch adjustment.
5.3
Connecting the warning lights
A warning light (e.g. SLK-L) may be connected to the control.
Connect the warning light (
24 V DC/max. 3 W
) to terminals
E4
and
E5
(
not
fl oating,
24 V DC
).
The function is set in menu