63/71
User Manual for hybrid inverter HYD 10-20KTL-3PH - Rev. 1.0 of 25/08/2020
Identification: MD-AL-GI-00
Identification: MD-AL-GI-00
Rev. 4.0 of 31.01.18 - Application: GID
5
protection 5
ID055
TempFault_HeatSin
6
Radiator
temperature
protection 6
ID057
TempFault_Env1
Ambient
temperature
protection 1
ID058
TempFault_Env2
Ambient
temperature
protection 2
ID059
TempFault_Inv1
Module 1 temperature
protection
ID060
TempFault_Inv2
Module 2 temperature
protection
ID061
TempFault_Inv3
Module 3 temperature
protection
ID065
VbusRmsUnbalanc
e
RMS bus voltage is not
balanced
Internal inverter errors. Switch it off,
wait 5 minutes and switch it on again.
If the errors still occur, contact
technical support.
ID066
VbusInstantUnbala
nce
Transient voltage value
of the BUS is not
balanced
ID067
BusUVP
Busbar
undervoltage
during grid connection
ID068
BusZVP
Low BUS voltage
ID069
PVOVP
PV overvoltage
Check whether the voltage of the PV
modules in series (Voc) is higher than
the maximum input voltage. If so,
adjust the number of PV modules in
series to reduce the voltage of the PV
modules in series, adapting them to
the input voltage range of the
inverter. After changing the voltage,
the inverter returns to normal
operation on its own.
ID070
BatOVP
Batter overvoltage
Check that the battery overvoltage
settings are compatible with the
battery specifications.
ID071
LLCBusOVP
LLC Bus overvoltage
protection
Internal inverter errors. Switch it off,
wait 5 minutes and switch it on again.
If the errors still occur, contact
technical support.
ID072
SwBusRmsOVP
Software
RMS
overvoltage protection
of the DC bus