In the three-phase meter, which is supplied separately, PIN5 and PIN6 are used for the communication
and correspond respectively to numbers 24 and 25. For more details, refer to the datasheets available
at
Figure 32 – Meter (1)
Phases R, S, T must be connected with the respective PINs 2, 5, 8 and the neutral cable N with PIN 10.
As regards the connections with the CTs, the terminals of the sensor positioned on phase R must be
connected to PIN 1 (red wire) and PIN 3 (black wire).
The terminals of the sensor positioned on phase S must be connected to PIN 4 (red wire) and PIN 6
(black wire).
The terminals of the sensor positioned on phase T must be connected to PIN 7 (red wire) and PIN 9
(black wire).
Position the sensors according to the indication on the sensor itself (in the direction of the arrow).
Figure 33- Meter (2)