User Manual for hybrid inverter HYD 10-20KTL-3PH - Rev. 1.0 of 25/08/2020
Identification: MD-AL-GI-00
Identification: MD-AL-GI-00
Rev. 4.0 of 31.01.18 - Application: GID
3.
Connect the cable to the terminal, according to the identification on the terminal.
Figure 21 - Connecting the cable to the terminal
4.
Connect the terminal to the machine port and turn the clamp in a clockwise direction.
Figure 22 - Terminal clamping
4.5.
Grid connection
The inverter is equipped with an integrated unit for monitoring the residual current; when the
inverter detects that the residual current exceeds 300mA, the connection to the grid will be quickly
disconnected.
If the external AC circuit breaker has a leakage protection function, its rated leakage action current
must be ≥ 300mA.
Procedure:
1.
Select the type of cable and the appropriate specifications according to Table 6.
2.
Pass the wire through the terminal.
Figure 23 - Passing of the wire through the terminal
3.
Connect the wire to the terminal, according to the identification on the terminal.