38/71
User Manual for hybrid inverter HYD 10-20KTL-3PH - Rev. 1.0 of 25/08/2020
Identification: MD-AL-GI-00
Identification: MD-AL-GI-00
Rev. 4.0 of 31.01.18 - Application: GID
*3. Importing of safety parameters
Find the file with the safety parameters
(renamed according to the country
selected) on the website, download
them to a USB stick and import them
4. Setting of input channel
Default order: BAT1, BAT2, PV1, PV2
*5. Setting of battery parameters
The default values are shown according
to the input channel configured
6. The set-up is completed
Table 16 - Parameters to be set for first start-up
NB:
Zucchetti Centro Sistemi S.p.A. shall not be held responsible for any harmful
consequences resulting from the incorrect setting of the country code.
With reference to point *5 in Table 16. To set the battery parameters, refer (as shown in the example)
to the configuration of the input channel. Start with battery 1 and, using the same procedure, continue
to battery n.
Battery type
Type of band communication protocol
Lead acid or no protocol type
1.Battery Address
1.Battery Capacity
2.Battery Charge Current Limit
2.Battery Nominal Voltage
3.Battery Discharge Current Limit
3.Battery Cell Type
4.Battery DOD (EOD)
4.Battery Charge Current Limit
5.Battery Discharge Current
Limit
6.Battery DOD (EOD)
It is very important to make sure that the right country code has been selected
in accordance with the requirements of the local energy authorities.
It is advisable to consult with qualified and authorised personnel to ensure the
correct choice
Caution