User Manual for hybrid inverter HYD 10-20KTL-3PH - Rev. 1.0 of 25/08/2020
Identification: MD-AL-GI-00
Identification: MD-AL-GI-00
Rev. 4.0 of 31.01.18 - Application: GID
2.Battery Address
5.Discharge Depth
3.Max Charge (A)
6.Save
OK
Depth of Discharge (DOD)
e.g. DOD = 50% and EPS = 80%
While the grid is connected, the inverter will not discharge the battery as long as the SOC is less than
50%.
In the event of a blackout, the inverter operates in EPS mode (if EPS is enabled) and continues to
discharge the battery until it reaches a battery SOC of 20%.
5.Depth of Discharge
OK
Depth of Discharge
50%
EPS of Depth of Discharge
80%
EPS Restore Depth
20%
2. Anti-Reflux
The “Anti Reflux Control” mode can be enabled to limit the maximum power exported to the grid. The
power set is the maximum power to be fed into the grid.
2.Anti Reflux
OK
1.Anti Reflux Control
OK
Enable
Disable
2.Reflux Power
OK
***KW
3. IV Curve Scan
The IV curve scan (MPP scan) can be enabled to find the maximum overall power by adjusting the
value during operation to obtain the maximum output from the panels even in suboptimal conditions.
A scan period can be set, or an instant scan can be performed.