47/71
User Manual for hybrid inverter HYD 10-20KTL-3PH - Rev. 1.0 of 25/08/2020
Identification: MD-AL-GI-00
Identification: MD-AL-GI-00
Rev. 4.0 of 31.01.18 - Application: GID
↓
Press “Ok”
Self-Test OK!
↓
Press “Down”
59.S1 threshold 253V 900ms
↓
Press “Down”
59.S1: 228V 902ms
↓
Press “Down”
59.S2 threshold 264.5V 200ms
↓
Press “Down”
59.S2: 229V 204ms
↓
Press “Down”
27.S1 threshold 195.5V 400ms
↓
Press “Down”
27.S1: 228V 408ms
↓
Press “Down”
27.S2 threshold 92V 200ms
↓
Press “Down”
27.S2: 227V 205ms
↓
Press “Down”
81>.S1 threshold 50.5Hz 100ms
↓
Press “Down”
81>.S1 49.9Hz 103ms
↓
Press “Down”
81>.S2 threshold 51.5Hz 100ms