2-10
Reference Guide
Model No.
Running Head
Ringing Generators
System Installation
1. . The 890620 may be installed with power applied (“Hot swapping”). The 890620 ring
generator has improved operating efficiency resulting in lower operating temperatures
which promote a longer life expectancy and support of more analog voice ports per ring
generator. It also provides inrush current control during start-up allowing for hot insertion
(plugging) without disrupting the Integrated Access System power supply busses.
2. Make sure jumper W201 is installed if this is the only ringing generator in the unit, if it is
the MASTER ringing generator, refer to Figure 2-5. If this is a SLAVE ringing generator,
cut jumper W201 with wire cutters.
3. Remove the rear panel covering the rear power slots. Insert the ringing generator into slot
R1 or R2.
4. Hold the unit by its metal handle and align the PCB edges with the slot rail guides in the
power supply backplane. Gently push the unit in until it is firmly seated in the backplane
connector.
5. If the power supply is installed and power is on, the LED on the front panel of the ringing
generator should illuminate green. A problem exists if the LED is not illuminated. Verify
that the MASTER/SLAVE settings are correct, and that the unit is firmly seated in the
connector. If so, replace the ringing generator (it is faulty).
6. Replace the panel cover.
Figure 2-5. 105V Ringing Generator Jumper Setting
Power
Bus
Edge
Connector
Slave
Master
JP1
Master/Slave
Jumper
JP2
Содержание IMACS 8000
Страница 20: ...xviii Table of Contents Model No Running Head Table of Contents...
Страница 38: ...1 6 Reference Guide Model No Running Head Customer Service and Ordering Information What s New...
Страница 58: ...2 20 Reference Guide Model No Running Head Installing the Other Plug In Cards System Installation...
Страница 82: ...4 18 Reference Guide Model No Running Head PWE IP Uplink Server 8000 PWE Applications...
Страница 210: ...6 12 Reference Guide Model No Running Head Performance Monitoring System Testing and Diagnostics...
Страница 270: ...7 60 System Cards Model No Running Head CPU Card Specifications CPU Card...
Страница 300: ...8 30 System Cards Model No Running Head Interface Card Specifications Interface Card...
Страница 337: ...System Cards 9 37 WAN Card WAN Card User Screens and Settings Figure 9 21 T1 WAN Cross Connect Screen display only...
Страница 352: ...9 52 System Cards Model No Running Head WAN Card Specifications WAN Card...
Страница 360: ...10 8 System Cards Model No Running Head Alarm Card Troubleshooting Alarm Cards...
Страница 382: ...11 22 Voice Cards Model No Running Head E M Card Specifications E M Card...
Страница 454: ...14 34 Data Cards Model No Running Head HSU Card User Screens and Settings HSU Card Figure 14 16 HSU Broadcast Screen...
Страница 474: ...14 54 Data Cards Model No Running Head HSU Card Specifications HSU Card...
Страница 484: ...15 10 Data Cards Model No Running Head OHSU Card Specification OHSU 4P Card...
Страница 536: ...18 8 Data Cards Model No Running Head DS0 DP Card Specifications DS0 DP Card...
Страница 596: ...21 38 Server Cards Model No Running Head IPR 4 Server Card Specifications IPR 4 Router Card...
Страница 614: ...22 18 Server Cards Model No Running Head ACS MCC Card Troubleshooting MCC Card...
Страница 644: ...24 18 Server Cards Model No Running Head PWE Card Troubleshooting PWE Card...
Страница 659: ...Reference Guide A 15 A 4 2 External Talk Battery Fuses Manufacturer Part NumberA3 Little Fuse 218 005 Bussman GDC 5...
Страница 674: ...A 30 Reference Guide Model No Running Head...
Страница 729: ...Pin Outs C 31 C 8 HSU Cards...
Страница 752: ...C 54 Pin Outs Model No Running Head...