Zehnder EASY 5.0
62
23.2. Frost protection
The frost protection of the cold water coil must be ensured by a sufficient concentration of anti-freeze liquid (MEG or
MPG) in accordance with the cold water generator and the temperature operating range of the cold water coil. If the use
of a frost protection thermostat is considered, it must be external to the machine.
23.3. Thermal output
To ensure thermal output, it is necessary to supply the cooling coil with the required volume, temperature and
concentration of anti-freeze (MEG or MPG) when selecting the material.
24. Control of the cold water pump
When the cooling sequence is active (cooling requirement > 0%) the DO output of the cold water pump control is
activated. When the requirement disappears (cooling requirement = 0%), the DO output of the controller is deactivated.
25. Control of the electric fresh air preheating coil
The purpose of the electric fresh air preheating coil is to maintain a sufficient temperature (factory setting -5°C) at the
fresh air inlet of the plate heat exchanger in order to avoid any risk of icing of the condensed water vapour on the return
air side. It is optional equipment that complements the modulating bypass (standard equipment) and ensures protection
against icing of the plate heat exchanger, particularly in cold climatic zones, and allows the machine's operating range
to be extended.
Access path to the function (Access level: Expert)
Step 1
→
Step 2
→
Step 3
→
Step 4
From
screen
Area to
click
Access path to the function (Access level: Expert)
Step 1
→
Step 2
→
Step 3
→
Step 4
From
screen
Area to
click
Actuators
Cooling output
Actuators
Electric preheating coil
Settings and configuration
Sensors
Alarms
PID loops
Functions
Actuators
Settings and configuration
Sensors
Alarms
PID loops
Functions
Actuators
Main menu
Main menu
Actuator settings 2/2
Actuator settings 2/2
Cooling
Cooling
Bypass exchanger
Bypass exchanger
Hot water coil
Electric heating coil
Heating output
Electric preheating coil
Electric preheating coil
Z-MASTER-V1122-CSY-INM-Zehnder Easy5.0