Zehnder EASY 5.0
45
Unit
Rea-
ding
Entry
Scaling
factor
Modbus
Factory
setting
Modbus
Type
Register
Modbus
Address
Modbus
Variable
Modbus
Address
BACnet
Details
Air law
temperature
setpoint external
temperature 4
°C
X
X
10
190
Holding
Register
828
short
AV, 30828
Used only if temperature
control
(supply or return) by air law
Air law
temperature
setpoint external
temperature 5
°C
X
X
10
180
Holding
Register
829
short
AV, 30829
Used only if temperature
control
(supply or return) by air law
Air law
temperature
setpoint external
temperature 6
°C
X
X
10
180
Holding
Register
830
short
AV, 30830
Used only if temperature
control
(supply or return) by air law
Air law
temperature
setpoint external
temperature 7
°C
X
X
10
230
Holding
Register
831
short
AV, 30831
Used only if temperature
control
(supply or return) by air law
Air law
temperature
setpoint external
temperature 8
°C
X
X
10
230
Holding
Register
832
short
AV, 30832
Used only if temperature
control
(supply or return) by air law
Supply air fan
normal speed
setpoint
%
X
X
10
70
Holding
Register
848
short
AV, 30848 Only for ECO and DIVA
versions
Supply air fan
reduced speed
setpoint
%
X
X
10
40
Holding
Register
847
short
AV, 30847 Only for ECO and DIVA
versions
Return air fan
normal speed
setpoint
%
X
X
10
70
Holding
Register
851
short
AV, 30851 Only for ECO and DIVA
versions
Return air fan
reduced speed
setpoint
%
X
X
10
40
Holding
Register
850
short
AV, 30850 Only for ECO and DIVA
versions
Supply air fan
normal pressure
setpoint
Pa
X
X
10
130
Holding
Register
836
short
AV, 30836 Only for LOBBY versions
Supply air fan
reduced pressure
setpoint
Pa
X
X
10
130
Holding
Register
835
short
AV, 30835 Only for LOBBY versions
Return air fan
normal pressure
setpoint
Pa
X
X
10
130
Holding
Register
839
short
AV, 30839 Only for LOBBY versions
Return air fan
reduced pressure
setpoint
Pa
X
X
10
130
Holding
Register
838
short
AV, 30838 Only for LOBBY versions
Supply air fan
normal air volume
setpoint
m
3
/h
X
X
0.1
See
details
Holding
Register
842
short
AV, 30842
Only for MAC2 and QUATTRO
versions, factory setting
depends on machine model
Supply air fan
reduced air volume
setpoint
m
3
/h
X
X
0.1
See
details
Holding
Register
841
short
AV, 30841
Only for MAC2 and QUATTRO
versions, factory setting
depends on machine model
Return air fan
normal air volume
setpoint
m
3
/h
X
X
0.1
See
details
Holding
Register
845
short
AV, 30845
Only for MAC2 and QUATTRO
versions, factory setting
depends on machine model
Z-MASTER-V1122-CSY-INM-Zehnder Easy5.0