Zehnder EASY 5.0
68
28. LOBBY pressure transducers
The LOBBY pressure transducer is a differential pressure transducer.
It converts the pressure difference between the atmospheric pressure and the pressure in the associated air stream
(supply or return) into an analogue signal that can be evaluated by the controller.
Its output signal is 0-10V and directly proportional to the measured differential pressure.
For the LOBBY machine versions, the air pressure is also used as a feedback signal for the fans. When the measured
pressure is below a certain threshold (25 Pa factory setting for all machines), the controller interprets this as a fan
malfunction and may activate certain alarms. If an electric heating coil is used, it is only activated if the pressure is
higher than the return pressure threshold of the supply air fan. This is an activation condition.
The LOBBY pressure transducer is identical for all machines.
Reference point
Details
1
Setting jumpers
2
Zero setting (sensor must be in its operating position,
pressure taps disconnected and fans off)
3
Electrical connection terminal block
4
Pressure taps P1(+) et P2(-)
Max. differential pressure rating = 1600 Pa
The jumpers are in the OFF position (position 0)
Z-MASTER-V1122-CSY-INM-Zehnder Easy5.0
TRPS/TRPR pressure transducer
LOBBY
Differential pressure (Pa) measured between P1(+) and P2(-)