63
It operates in an on/off mode based on an algorithm that compares the actual value of the fresh air inlet temperature in
the plate heat exchanger with the setpoint. The electric fresh air preheating coil therefore only comes into operation
when the outside air temperature is below -5°C.
The sequence is managed by a PID. The DO output that powers the resistor is of the on-off type (all or nothing).
This sequence is independent of the heating, recovery, cooling and anti-icing bypass sequences.
The electric fresh air preheating coil is equipped with an NC (normally closed) safety thermostat (THSD) set at +100°C,
which cuts off the power supply to the KD contact transmitter control circuit when activated to protect the machine from
overheating.
Z-MASTER-V1122-CSY-INM-Zehnder Easy5.0
Return air
Bypass
SBD
Electric defrosting
coil DBE
(preheating)
Preheating temperature setpoint (-5°C)
Fresh air
Exhaust air
Supply air
VAS
VAR
Fresh air temperature at the plate heat exchanger inlet
Status of the digital output for controlling the fresh air preheating coil
Temperature setpoint
Anti-icing protection
-5
°C
time
time
Active
Idle