Zehnder EASY 5.0
32
Id
Description
Class
Time
limit
Action
Value/thres-
hold
Details/explanations
Possible causes
6
Return air fan
(VAR) fault
A
120s Normal
stop*
See Id=1
supply air
fan (VAS)
fault
See Id=1 supply air fan
(VAS) fault
See Id=1 supply air fan (VAS) fault
44
Rotary heat
exchanger
alarm
C
600s
The operational feedback
from the control-command
box of the rotary heat
exchanger was not
received within the time
limit.
The machine continues to
operate without energy
recovery.
The wheel is blocked or has a
mechanical rotational defect.
The belt is broken or slipping.
The drive motor has a malfunction.
The run command (K2-wheel relay)
or the power supply to the control-
command box has a fault /
malfunction.
The control-command box of the
rotary heat exchanger is defective.
53
Supply and
return filter
alarm
C
600s
The pressure drop of the
supply and/or return filters
has exceeded the set value
(300Pa for M5 + F7 filters,
200Pa for F7 filter, 150Pa
for M5 filter) of the
corresponding filter
pressure switch.
Clogged filter.
Unsuitable filter (third-party supply
does not meet manufacturer's
requirements).
Unsuitable filtration class.
An external element obstructs the
air flow in the machine.
54 Return filter
alarm
C
600s
See Id=53 Supply and
return filter alarm
See Id=53 Supply and return filter
alarm
56
Frost
protection
alarm (THA)
C
120s Rapid
stop**
The frost protection
thermostat (THA) has
detected a hot water coil
temperature below its set
value (5°C factory setting).
When the alarm is active,
the unit stops immediately
without a post-ventilation
sequence and the hot
water coil output is forced
to 100% (10V); see
details/explanations in the
rest of the document
(XXI.2 Frost protection
thermostat (THA))
The hot water coil supply pump does
not work (no air volume).
The 3-way temperature control
valve remains closed.
The hot water generator is not
working or supplies water that is too
cold.
The thermostat setting has been
changed.
The thermostat is faulty.
The wiring/cable between the
thermostat and the controller is
faulty.
58 Fire alarm
C
1s
The behaviour of the
machine depends on how
the anti-fire function is
configured by the user.
When leaving the factory,
the anti-fire function is not
activated, so it is not
functional. Depending on
the settings made during
commissioning, the
activation of the anti-fire
function can affect the
operation of the unit, the
fans, the isolation dampers
and the bypass (if plate
heat exchanger).
The DI input is active (dry contact
closed).
Z-MASTER-V1122-CSY-INM-Zehnder Easy5.0