Zehnder EASY 5.0
44
16.6.2. Setpoints
Unit
Rea-
ding
Entry
Scaling
factor
Modbus
Factory
setting
Modbus
Type
Register
Modbus
Address
Modbus
Variable
Modbus
Address
BACnet
Details
Setpoint of
operating mode
-
X
X
1
0
Holding
Register
796
short
MSV,
30796
Modbus:
0=Inactive/1=reduced
operation/
2=normal operation/
4=AHU stop
BACnet:
1=Inactive/2=reduced
operation/
3=normal operation/
5=AHU stop
Constant supply
temperature
setpoint
°C
X
X
10
180
Holding
Register
811
short
AV,30811
Used only if temperature
control
of constant supply
Constant return
temperature
setpoint
°C
X
X
10
180
Holding
Register
812
short
AV, 30812
Used only if temperature
control
of constant return
Outdoor
temperature 1 air
law
°C
X
X
10
-200
Holding
Register
817
short
AV, 30817
Used only if temperature
control
(supply or return) by air law
Outdoor
temperature 2 air
law
°C
X
X
10
-50
Holding
Register
818
short
AV, 30818
Used only if temperature
control
(supply or return) by air law
Outdoor
temperature 3 air
law
°C
X
X
10
100
Holding
Register
819
short
AV, 30819
Used only if temperature
control
(supply or return) by air law
Outdoor
temperature 4 air
law
°C
X
X
10
150
Holding
Register
820
short
AV, 30820
Used only if temperature
control
(supply or return) by air law
Outdoor
temperature 5 air
law
°C
X
X
10
200
Holding
Register
821
short
AV, 30821
Used only if temperature
control
(supply or return) by air law
Outdoor
temperature 6 air
law
°C
X
X
10
250
Holding
Register
822
short
AV, 30822
Used only if temperature
control
(supply or return) by air law
Outdoor
temperature 7 air
law
°C
X
X
10
350
Holding
Register
823
short
AV, 30823
Used only if temperature
control
(supply or return) by air law
Outdoor
temperature 8 air
law
°C
X
X
10
400
Holding
Register
824
short
AV, 30824
Used only if temperature
control
(supply or return) by air law
Air law
temperature
setpoint external
temperature 1
°C
X
X
10
250
Holding
Register
825
short
AV, 30825
Used only if temperature
control
(supply or return) by air law
Air law
temperature
setpoint external
temperature 2
°C
X
X
10
230
Holding
Register
826
short
AV, 30826
Used only if temperature
control
(supply or return) by air law
Air law
temperature
setpoint external
temperature 3
°C
X
X
10
200
Holding
Register
827
short
AV, 30827
Used only if temperature
control
(supply or return) by air law
Z-MASTER-V1122-CSY-INM-Zehnder Easy5.0