Zehnder EASY 5.0
47
Reading Entry
Type
Register
Modbus
Address
Modbus
Variable
Modbus
Address
BACnet
Details
Hot water coil frost
protection fault
X
Input
Status
66
bool
BV, 20066
0=no alarm / 1=alarm present
Only for machine equipped with a hot water heating
coil
Rotary heat
exchanger fault
X
Input
Status
54
bool
BV, 20054
0=no alarm / 1=alarm present
Only for machine equipped with rotary heat
exchanger
Fresh air
temperature
sensor fault
X
Input
Status
154
bool
BV, 20154 0=no alarm / 1=alarm present
Supply air
temperature
sensor fault
X
Input
Status
156
bool
BV, 20156 0=no alarm / 1=alarm present
Exhaust air
temperature
sensor fault
X
Input
Status
157
bool
BV, 20157
0=no alarm / 1=alarm present
Only for machine equipped with plate heat
exchanger
Return air
temperature
sensor fault
X
Input
Status
158
bool
BV, 20158 0=no alarm / 1=alarm present
Preheated air
temperature
sensor fault
X
Input
Status
191
bool
BV, 20191
0=no alarm / 1=alarm present
Only for machine equipped with plate heat
exchanger
Supply pressure
transducer fault
X
Input
Status
175
bool
BV, 20175 0=no alarm / 1=alarm present
Return pressure
transducer fault
X
Input
Status
176
bool
BV, 20176 0=no alarm / 1=alarm present
Supply air volume
transducer fault
X
Input
Status
177
bool
BV, 20177 0=no alarm / 1=alarm present
Return volume
transducer fault
X
Input
Status
178
bool
BV, 20178 0=no alarm / 1=alarm present
CO
2
transducer
fault
X
Input
Status
185
bool
BV, 20185 0=no alarm / 1=alarm present
Only for DIVA and QUATTRO versions
Anti-fire fault
X
Input
Status
68
bool
BV, 20068 0=no alarm / 1=alarm present
Manual mode
output fault
X
Input
Status
148
bool
BV, 20148 0=no alarm / 1=alarm present
Supply air fan
difference
X
Input
Status
92
bool
BV, 20092 0=no alarm / 1=alarm present
Return air fan
difference
X
Input
Status
93
bool
BV, 20093 0=no alarm / 1=alarm present
Supply
temperature too
high
X
Input
Status
96
bool
BV, 20096 0=no alarm / 1=alarm present
Z-MASTER-V1122-CSY-INM-Zehnder Easy5.0