EN - 28 - For the installer
K
J
M
O
N
I
L
Use a soft brush to clean the fan impellers.
Use a vacuum cleaner to remove dust.
Do not damage the fan impellers.
Do not damage the temperature sensor.
•
Install
all parts in reverse order.
•
Carry out
the self-test in accordance with
menu P76.
Install the leakage tray correctly underneath
the heat exchanger. The slanting side of the
leakage tray must be on the side of the con-
densation drain.
During assembly of the heat exchanger,
check the position of the four rubber seals.
Check the condensation drain once every
two years.
Fasten the screws to a maximum of 1.5 Nm.
This is roughly equal to speed 2 of an aver-
age battery-powered drill.
3.9.2 Cleaning the fi lter if a pre-heater is fi tted
The fi lter of the pre-heater (if fi tted) must be cleaned
once every 4 years:
•
Disconnect
the power from the ComfoAir.
•
Remove
fi lters (B) from the ComfoAir.
•
Release
the front panel by unscrewing the
screws (C).
•
Slide
the front panel upwards and
remove
it
from the ComfoAir.
•
Release
the cover panel by unscrewing the
screws (D).
•
Remove
the screw from the electronics car-
riage.
•
Pull
the electronics carriage carefully forwards.
•
Release
the connectors (J) and the earth wire
on the PCB panel and fully
remove
the cables
including the two grommets (K).
•
Remove
the cable (P) from the PCB panel.
•
Remove
the pre-heater holder by sliding it up
halfway and then pulling it away from the valve.
•
Remove
the pre-heater fi lter located behind the
pre-heater holder.
•
Clean
the fi lter with a brush.
•
Remove
any deposit using a damp cloth.
•
Install
all parts in reverse order.
•
Carry out
the self-test in accordance with
menu P76.
The hollow side of the pre-heater
fi
lter must
face the pre-heater holder.
Fasten the screws to a maximum of 1.5 Nm.
This is roughly equal to speed 2 of an aver-
age battery-powered drill.
3.10 Malfunctions
If the ComfoAir suffers a malfunction, then in most
cases a malfunction alert will appear on the screen
of the digital operating device.
However, malfunction alerts may not appear on the
digital operating device in all cases, even though
there is a malfunction (or problem). A concise ex-
planation of both types of malfunction (or problem)
is given in the paragraphs below.
3.10.1 Malfunction alerts on the digital
operating device
Below is a list of the malfunction alerts on digital
operating device.
Code
Description
A0
NTC sensor Tge is defective. (= geo-
thermal heat exchanger temperature)
A1
NTC sensor T1 is defective.
(= outside air temperature)
A2
NTC sensor T2 is defective.
(= supply air temperature)
A3
NTC sensor T3 is defective.
( =return air temperature)
A4
NTC sensor T4 is defective.
(= exhaust air temperature)
A5
Malfunction in the bypass motor.
A6
Malfunction in the
Pre-heater motor.
A7
Pre-heater does not heat
suffi ciently.
A8
Pre-heater becomes too hot.
A9
Moisture sensor defective.
A10
N/a
A11
NTC sensor Tah is defective.
(= afterheater temperature)
E1
Exhaust fan not rotating.
E2
Supply fan not rotating.
E4
Heat recovery mode deactivated.
EA1
Enthalpy sensor measures excessive
humidity.
EA2
No communication with the
enthalpy sensor.
‚Fil‘ ‚tEr‘ Internal fi lter is dirty
FilterI
Internal fi lter is dirty
FilterE
External fi lter is dirty
NC
Not Connected
Prevent water from entering the electrical
connections.