3
EN - 22 - For the installer
Menu P5 Setting additional programmes
Additional programme values
Submenu
Description
Minimum
Maximum
Default
P50
Activation of the
open fi re programme.
0 (= No)
1 (= Yes)
0
P51
Confi rming the presence of
a pre-heater.
0 (= No)
1 (= Yes)
0
Note:
Only change if a pre-heater is installed afterwards.
If the ComfoAir must be reset to the original factory settings using P75, the default
value of the pre-heater is set to “
NOT
FITTED
”.
•
Check
the presence of the pre-heater following a general system reset
via menu P75.
P52
Setting the
frost-free programme.
•
0; Guaranteed protection.
•
1; High protection.
•
2; Nominal protection.
•
3; Economy.
0
3
2
Note:
In
GUARANTEED
PROTECTION
MODE
the pre-heater is switched on soonest; this level offers
the best guarantee of balanced ventilation. Vice versa, in
ECONOMY
MODE
the pre-heater
switches on at the last possible moment; balanced ventilation is not guaranteed in
this mode.
When commissioning the ComfoAir, the frost-free programme can usually be left at
level 2:
NOMINAL
MODE
(factory setting). In areas with frequent cold spells in winter (fre-
quent periods of -10°C or lower), level 1 should be selected:
HIGH
PROTECTION
or even
level 0:
GUARANTEED
PROTECTION
.
P53
N/a
0 (= No)
1 (= Yes)
0
Note:
Always keep this setting on Default
P54
Confi rming the presence of a bypass. 0 (= No)
1 (= Yes)
1
Note:
The standard ComfoAir confi guration includes a bypass. Therefore, leave the value
at ‘1’.
P55
Confi rming the presence of a
afterheater.
• 0; Afterheater not fi tted
• 1; Afterheater fi tted
• 2;
Afterheater is fi tted and is
regulated by a PWM signal.
0 (= No)
1 (= Yes)
0
P56
Setting the required
air volume in the house.
• nL: ”normal air volume”.
• HL: “high air volume”.
nL
HL
HL
Note:
Setting the air volume in P56 (to “nL” or “HL”) is the starting point
for programming the air specifi cations and setting the fans.
P57
Setting the ComfoAir type.
• Li = ”Left-hand version”.
• Re = ”Right-hand version”.
Li
Re
Li
Note:
The ComfoAir is correctly preprogrammed at the factory.
•
See also the identifi cation plate for these details.
P58
Enter controller priorities.
• 0;
Preference for High setting
INCLUDING analogue input.
• 1;
Preference to for High setting
EXCLUDING analogue input.
0
1
0