3
EN - 30 - For the installer
E3
Malfunction
ATTENTION!
Risk of electrocution:
do not touch the PCB,
the pre-heater
or the afterheater.
Set P53 to "0"
Reset the unit
E4
ComfoAir switched off
by auxiliary equipment
Cause depends on what
equipment is interfaced with
the ComfoAir:
check the relevant device
ATTENTION!
Risk of electrocution:
do not touch the PCB,
the pre-heater
or the afterheater.
A1 / A2 / A3 / A4
Temperature sensor malfunction
T1 / T2 / T3 / T4
Disconnect the power
Remove filters,
front and metal cover
Remove the
malfunctioning sensor's
connector from the PCB
Check the resistance of
the malfunctioning sensor
according to the adjacent table
Resistance okay?
Yes
No
Replace PCB
ATTENTION:
Reset unit!
Replace
temperature sensor
ATTENTION!
Risk of electrocution:
do not touch the PCB,
the pre-heater
or the afterheater.
Resistance [K
Ω
]
MIN.
MID.
MAX.
10
19,.570
19,904
20,242
15
15,485
15,712
15,941
18
13,502
13,681
13,861
19
12,906
13,071
13,237
20
12,339
12,491
12,644
21
11,801
11,941
12,082
22
11,291
11,420
11,550
25
9,900
10,000
10,100
30
7,959
8,057
8,155
Temperature
[°C]