background image

3

EN - 30 - For the installer

E3

Malfunction 

ATTENTION!

Risk of electrocution: 

do not touch the PCB, 

the pre-heater 

or the afterheater.

Set P53 to "0"

Reset the unit

E4

ComfoAir switched off 
by auxiliary equipment

Cause depends on what 

equipment is interfaced with 

the ComfoAir: 

check the relevant device

ATTENTION!

Risk of electrocution: 

do not touch the PCB, 

the pre-heater 

or the afterheater.

A1 / A2 / A3 / A4

Temperature sensor malfunction

T1 / T2 / T3 / T4

Disconnect the power

Remove filters, 

front and metal cover

Remove the 

malfunctioning sensor's 
connector from the PCB

Check the resistance of 

the malfunctioning sensor 

according to the adjacent table

Resistance okay?

Yes

No

Replace PCB

ATTENTION: 

Reset unit!

Replace 

temperature sensor

ATTENTION!

Risk of electrocution: 

do not touch the PCB, 

the pre-heater 

or the afterheater.

Resistance [K

Ω

]

MIN.

MID.

MAX.

10

19,.570

19,904

20,242

15

15,485

15,712

15,941

18

13,502

13,681

13,861

19

12,906

13,071

13,237

20

12,339

12,491

12,644

21

11,801

11,941

12,082

22

11,291

11,420

11,550

25

9,900

10,000

10,100

30

7,959

8,057

8,155

Temperature

[°C] 

Содержание ComfoAir 550 Luxe

Страница 1: ...ComfoAir 550 Luxe Manual...

Страница 2: ...II All rights reserved This manual has been compiled with the utmost care The publisher cannot be held liable for any damage caused as a result of missing or incorrect information in this manual...

Страница 3: ...eothermal heat exchanger optional 4 2 1 10 Enthalpy optional 4 2 1 11 Luxury versions extra options 4 2 2 Available operating devices 4 2 2 1 3 position switch 4 2 2 2 CO2 sensor 5 2 2 3 Bathroom swit...

Страница 4: ...ction of the air ducts 19 3 6 2 Connection of the condensation drain 19 3 7 Commissioning the ComfoAir 20 3 7 2 CC Ease panel 20 3 8 Programming air specifications 26 3 9 Maintenance by the installer...

Страница 5: ...Type Serial number Protecion class Insolation class 1 3 Guarantee and liability 1 3 1 Guarantee conditions The ComfoAir is covered by a manufacturer s war ranty for a period of 24 months after fitting...

Страница 6: ...ings com ments and instructions as prescribed in this manual at all times Store this manual in the vicinity of the ComfoAir for its entire working life Instructions with regard to cleaning or replacin...

Страница 7: ...s au tomatically All you have to do is set the required comfort temperature 2 1 4 Frost protection The ComfoAir is also fitted with a frost protection device This is an automatic protective system tha...

Страница 8: ...positions of the ComfoAir One or multiple 3 position switches can be fitted in the house e g in the kitchen The following types of switches can be used Type 1 J Standard 3 position switch Type 2 J 3...

Страница 9: ...ons of the bathroom switch can also be integrated into a light switch 2 2 4 CC Luxe panel The ComfoAir can be operated by means of a CC Luxe panel which can be ordered separately The CC Comfort Contro...

Страница 10: ...N With this button you can read or set the comfort temperature Press and hold for less than 2 second READ Press and hold for more than 2 second SET This button allows you to programme two settings Pre...

Страница 11: ...ork to the temperature set Reading the comfort temperature 1 Press briefly 2 Wait until the comfort temperature appears 3 Press again to return Setting the comfort temperature 1 Press longer than 2 se...

Страница 12: ...s 1 Press to increase the ventilation volume 2 Press to decrease the ventilation volume During manual ventilation the CC Ease panel will not display AUTO but MANUAL 3 Press to return to automatic vent...

Страница 13: ...e in hours using or Press again Wait until the minutes appear on the screen Select the desired time in minutes using or Press again Wait until the ventilation setting flashes Select the desired ventil...

Страница 14: ...lue for the programme using or 8 Press to confirm 9 Repeat steps 3 to 8 to set multiple ventilation programmes in succession The minimum and maximum values for the available ventilation programmes are...

Страница 15: ...n x minutes after operating the bathroom switch the ComfoAir switches to the HIGH POSITION 0 Min 15 Min 0 Min P22 Optional Note Only applies to systems fitted with a corded switch and a second switch...

Страница 16: ...back to the set level after x minutes 1 Min 120 Min 30 Min P27 Note Only applies to systems fitted with a CC Ease panel Time for the Boost setting After pressing continu ously 2 sec the ComfoAir runs...

Страница 17: ...g follow this procedure Press CC Ease panel for at least 4 seconds until the filter warning disappears Disconnect the power from the ComfoAir Remove handles A from the ComfoAir Remove the old filters...

Страница 18: ...malfunction indicators In the event of a malfunction or in the event of a filter dirty alert the indicator lights up Wireless 3 position switch with malfunction in dicator The malfunction indicators...

Страница 19: ...nnections C for the air ducts 2 G4 filters D for air purification 2 energy efficient DC motors E with high efficient fan HE High Efficient heat exchanger with optional moisture exchanger F Electronics...

Страница 20: ...h at 240 Pa 2 56 A Electricity Power supply 230 50 V Hz Cos phi 0 48 0 62 Supply fan noise level at 0 m Position Ventilation capacity Value LOW SETTING 150 m3 h at 23 Pa 50 dB A MEDIUM SETTING 250 m3...

Страница 21: ...the installer 17 EN 3 3 Dimension sketch 800 724 5 569 280 5 124 5 490 180 200 208 5 208 5 265 32 ELECTRICAL AND DATA CONNECTION CONDENSATION DRAIN LEFT HANDVERSION CONDENSATION DRAIN RIGHT HANDVERSI...

Страница 22: ...fitting both the intake and the ex haust connections of the ComfoAir with silenc ers located directly against the unit For more information please contact Zehnder A 10mm gap should be left under the i...

Страница 23: ...air Exhaust air Supply air Outside air ComfoAir Left Outside air Supply air Exhaust air Return air ComfoAir Right 3 6 2 Connection of the condensation drain Warm exhaust air is cooled by the outside...

Страница 24: ...g P menus P3 to P8 are intended sole ly for the installer The ComfoAir s bypass valve will not work for the first 4 minutes after a power cut un less the programme mode is activated 3 7 1 CC Ease pane...

Страница 25: ...nL HL 35 40 P36 Setting the capacity in of the supply fan in MEDIUM POSITION 17 99 nL HL 50 70 P37 Setting the capacity in of the supply fan in HIGH POSITION 18 100 nL HL 70 90 P38 Current capacity i...

Страница 26: ...can usually be left at level 2 NOMINAL MODE factory setting In areas with frequent cold spells in winter fre quent periods of 10 C or lower level 1 should be selected HIGH PROTECTION or even level 0 G...

Страница 27: ...at exchanger is fitted then the unregulated setting must be selected so that the ComfoAir s bypass valve continues to function properly P61 Setting the percentage by which the supply fan must increase...

Страница 28: ...d closes if fitted P77 Resetting filter dirty counter 0 1 0 Note This resets the counter that triggers a dirty filter alert on the ComfoAir This allows the filter to be cleaned or replaced before the...

Страница 29: ...1 0 841 0 control 1 programme analogue input 4 0 1 0 842 set point analogue input 4 programme 0 100 50 843 min setting analogue input 4 0 99 0 844 max setting analogue input 4 0 100 100 845 0 positiv...

Страница 30: ...3 seconds on and untill InR appears on the CC Ease panel In programming mode the bypass and pre heater valves are always closed After 30 minutes the ComfoAir automatically termi nates the programming...

Страница 31: ...ed edge to ensure a good seal Pull the strap E to remove the heat exchanger and the leakage tray F E F Remove the heat exchanger from the leakage tray F The heat exchanger may contain water resi dues...

Страница 32: ...t using a damp cloth Install all parts in reverse order Carry out the self test in accordance with menu P76 The hollow side of the pre heater filter must face the pre heater holder Fasten the screws t...

Страница 33: ...wnwards Reconnect the power Press until malfunction disappears E1 E2 Exhaust supply fan malfunction Remove filters front and metal cover Does the fan connection on the PCB register 230 VAC Yes Activat...

Страница 34: ...T2 T3 T4 Disconnect the power Remove filters front and metal cover Remove the malfunctioning sensor s connector from the PCB Check the resistance of the malfunctioning sensor according to the adjacent...

Страница 35: ...es Yes Replace cog No Disconnect the power and replace PCB ATTENTION Reset unit Disconnect the power and replace motor ATTENTION Risk of electrocution do not touch the PCB the pre heater or the afterh...

Страница 36: ...Disconnect the power Remove filters front and metal cover Unplug Pre heater from the PCB Is resistance of Pre heater plug 300 ohms Yes Remove exchanger and Pre heater Is resistance of Pre heater cable...

Страница 37: ...anger Fan dirty Clean the fan Ventilation ducts blocked Clean the ventilation ducts ComfoAir is in frost protection opera tion Too noisy Fan bearings defective Replace the fan bearings Fan settings Ch...

Страница 38: ...rature sensor T1 T3 in top of unit near the electronic carriage 400300025 4 Temperature sensor T2 T4 in scroll casing of both fans 400300026 5 Forst free element 400300027 6 Filter 2x 400100030 7 Filt...

Страница 39: ...ite Yellow 0 10V Blue Green Yellow Green Yellow RS232 PC GND 12V Eb Ea GND 12V 12V Ab CCb Aa CCa GND GND Ext Comm N L3 PE Comm Basis RS232 KFB 12V RX TX ERR GND OFF BS GND GND FIE CH GND GND Tch Tge G...

Страница 40: ...White Brown White Brown White Yellow 0 10V Blue RS232 PC GND 12V Eb Ea GND 12V 12V Ab CCb Aa CCa GND GND Ext Comm N L3 PE Comm Basis RS232 KFB 12V RX TX ERR GND OFF BS GND GND FIE CH GND GND Tch Tge...

Страница 41: ...erial number where available Location of fan units 1 2 3 4 5 1 3 Installation Engineer s Details Engineer s Name Company Address Line 1 Address Line 2 Telephone Number Post Code 1 4 Commissioning Engi...

Страница 42: ...ystem installation clauses been followed as details in Tables 1 3 5 and 7 as applicable Yes No If any deviation from Tables 1 3 5 and 7 these should be detailed here Description of installed controls...

Страница 43: ...tection packaging been removed including background ventila tors such that system is fully functional Yes No For ducted systems has the ductwork installation been installed in such manner that air res...

Страница 44: ...Table 5 1a in ADF Extract Fan 1 Extract Fan 2 Extract Fan 3 Extract Fan 4 Extract Fan 5 For kitchen extract canopies only the highest setting needs to be recorded 3 3 Air Flow Measurements Extract Sys...

Страница 45: ...l s Refer to Table 5 1b ADF Measured Air Flow Low Rate l s Design Air Flow Low Rate l s Refer to Table 5 1b in ADF Living Room 1 Living Room 2 Dining Room Bedroom 1 Bedroom 2 Bedroom 3 Bedroom 4 Bedr...

Страница 46: ...694 Company register Zwolle 05022293 EG declaration of conformity Machine description Heat recovery units ComfoAir range Complies with the following directives Machinery Directive 98 37 EG Low Voltage...

Страница 47: ...1 43...

Страница 48: ...1 44 Zehnder Comfosystems Unit 1 Brookside Avenue Rustington West Sussex BN16 3LF J E Stork Ventilatoren B V 849050686 0709...

Отзывы: