For the installer - 27 - EN

3.9 

Maintenance by the installer

As a fi tter of the ComfoAir, you must carry out the 
following maintenance:
• 

Inspecting the heat exchanger and fans;

• 

Cleaning the fi lter (if Pre-heater is 
fi tted).

A concise explanation of these maintenance activi-
ties is given in the paragraphs below.

 Failure to carry out (periodic) maintenance 
on the ComfoAir ultimately compromises the 
performance of the ventilation system.

3.9.1  Inspecting the heat exchanger and fans

The fans and the heat exchanger must be inspected 
once every 4 years.
• 

Disconnect

 the power from the ComfoAir.

• 

Remove

 fi lters (B) from the ComfoAir.

• 

Release

 the front panel by unscrewing the 

screws (C).

• 

Slide

 the front panel upwards and 

remove

 the 

front panel from the ComfoAir.

• 

Release

 the cover panel by unscrewing the 

screws (D).

 A

 C 

 

When reassembling the front cover, the 
lower section must 

fi

 rst be inserted be-

hind the raised edge to ensure a good 
seal.

• 

Pull

 the strap (E) to remove the heat exchanger 

and the leakage tray (F).

• 

Remove

 the heat exchanger from the leakage tray 

(F).

 The heat exchanger may contain water resi-
dues!

• 

Clean

 the heat exchanger, if required.

 – 

 

Submerge

 the heat exchanger in hot water 

(max. 40 °C).

 – 

 

Rinse

 the heat exchanger with clean hot tap 

water (max. 40 °C).

 – 

 

Clasp

 the heat exchanger between both 

hands (on the coloured side surfaces) and 
shake the water from the heat exchanger.

 Do not use aggressive cleaning agents or 
solvents.

Do not 

re-install the heat exchanger yet. The fans 

also need to be inspected. The steps below explain 
how to remove, inspect and (if required) clean the 
fans (after cleaning the heat exchanger) :
• 

Remove

 the screw from the electronics car-

riage.

• 

Pull

 the electronics carriage carefully forwards.

• 

Release

 the connectors (J) and the earth wire  

on the PCB panel and fully remove the cables 
including the two grommets (K).

• 

Remove

 the entire scroll casing (L) by pressing 

the click fasteners (M).

• 

Remove

 the infl ow nozzle (N) by pressing the 

click fasteners surrounding the scroll casing.

• 

Clean

 the fans (O).

Содержание ComfoAir 550 Luxe

Страница 1: ...ComfoAir 550 Luxe Manual...

Страница 2: ...II All rights reserved This manual has been compiled with the utmost care The publisher cannot be held liable for any damage caused as a result of missing or incorrect information in this manual...

Страница 3: ...eothermal heat exchanger optional 4 2 1 10 Enthalpy optional 4 2 1 11 Luxury versions extra options 4 2 2 Available operating devices 4 2 2 1 3 position switch 4 2 2 2 CO2 sensor 5 2 2 3 Bathroom swit...

Страница 4: ...ction of the air ducts 19 3 6 2 Connection of the condensation drain 19 3 7 Commissioning the ComfoAir 20 3 7 2 CC Ease panel 20 3 8 Programming air specifications 26 3 9 Maintenance by the installer...

Страница 5: ...Type Serial number Protecion class Insolation class 1 3 Guarantee and liability 1 3 1 Guarantee conditions The ComfoAir is covered by a manufacturer s war ranty for a period of 24 months after fitting...

Страница 6: ...ings com ments and instructions as prescribed in this manual at all times Store this manual in the vicinity of the ComfoAir for its entire working life Instructions with regard to cleaning or replacin...

Страница 7: ...s au tomatically All you have to do is set the required comfort temperature 2 1 4 Frost protection The ComfoAir is also fitted with a frost protection device This is an automatic protective system tha...

Страница 8: ...positions of the ComfoAir One or multiple 3 position switches can be fitted in the house e g in the kitchen The following types of switches can be used Type 1 J Standard 3 position switch Type 2 J 3...

Страница 9: ...ons of the bathroom switch can also be integrated into a light switch 2 2 4 CC Luxe panel The ComfoAir can be operated by means of a CC Luxe panel which can be ordered separately The CC Comfort Contro...

Страница 10: ...N With this button you can read or set the comfort temperature Press and hold for less than 2 second READ Press and hold for more than 2 second SET This button allows you to programme two settings Pre...

Страница 11: ...ork to the temperature set Reading the comfort temperature 1 Press briefly 2 Wait until the comfort temperature appears 3 Press again to return Setting the comfort temperature 1 Press longer than 2 se...

Страница 12: ...s 1 Press to increase the ventilation volume 2 Press to decrease the ventilation volume During manual ventilation the CC Ease panel will not display AUTO but MANUAL 3 Press to return to automatic vent...

Страница 13: ...e in hours using or Press again Wait until the minutes appear on the screen Select the desired time in minutes using or Press again Wait until the ventilation setting flashes Select the desired ventil...

Страница 14: ...lue for the programme using or 8 Press to confirm 9 Repeat steps 3 to 8 to set multiple ventilation programmes in succession The minimum and maximum values for the available ventilation programmes are...

Страница 15: ...n x minutes after operating the bathroom switch the ComfoAir switches to the HIGH POSITION 0 Min 15 Min 0 Min P22 Optional Note Only applies to systems fitted with a corded switch and a second switch...

Страница 16: ...back to the set level after x minutes 1 Min 120 Min 30 Min P27 Note Only applies to systems fitted with a CC Ease panel Time for the Boost setting After pressing continu ously 2 sec the ComfoAir runs...

Страница 17: ...g follow this procedure Press CC Ease panel for at least 4 seconds until the filter warning disappears Disconnect the power from the ComfoAir Remove handles A from the ComfoAir Remove the old filters...

Страница 18: ...malfunction indicators In the event of a malfunction or in the event of a filter dirty alert the indicator lights up Wireless 3 position switch with malfunction in dicator The malfunction indicators...

Страница 19: ...nnections C for the air ducts 2 G4 filters D for air purification 2 energy efficient DC motors E with high efficient fan HE High Efficient heat exchanger with optional moisture exchanger F Electronics...

Страница 20: ...h at 240 Pa 2 56 A Electricity Power supply 230 50 V Hz Cos phi 0 48 0 62 Supply fan noise level at 0 m Position Ventilation capacity Value LOW SETTING 150 m3 h at 23 Pa 50 dB A MEDIUM SETTING 250 m3...

Страница 21: ...the installer 17 EN 3 3 Dimension sketch 800 724 5 569 280 5 124 5 490 180 200 208 5 208 5 265 32 ELECTRICAL AND DATA CONNECTION CONDENSATION DRAIN LEFT HANDVERSION CONDENSATION DRAIN RIGHT HANDVERSI...

Страница 22: ...fitting both the intake and the ex haust connections of the ComfoAir with silenc ers located directly against the unit For more information please contact Zehnder A 10mm gap should be left under the i...

Страница 23: ...air Exhaust air Supply air Outside air ComfoAir Left Outside air Supply air Exhaust air Return air ComfoAir Right 3 6 2 Connection of the condensation drain Warm exhaust air is cooled by the outside...

Страница 24: ...g P menus P3 to P8 are intended sole ly for the installer The ComfoAir s bypass valve will not work for the first 4 minutes after a power cut un less the programme mode is activated 3 7 1 CC Ease pane...

Страница 25: ...nL HL 35 40 P36 Setting the capacity in of the supply fan in MEDIUM POSITION 17 99 nL HL 50 70 P37 Setting the capacity in of the supply fan in HIGH POSITION 18 100 nL HL 70 90 P38 Current capacity i...

Страница 26: ...can usually be left at level 2 NOMINAL MODE factory setting In areas with frequent cold spells in winter fre quent periods of 10 C or lower level 1 should be selected HIGH PROTECTION or even level 0 G...

Страница 27: ...at exchanger is fitted then the unregulated setting must be selected so that the ComfoAir s bypass valve continues to function properly P61 Setting the percentage by which the supply fan must increase...

Страница 28: ...d closes if fitted P77 Resetting filter dirty counter 0 1 0 Note This resets the counter that triggers a dirty filter alert on the ComfoAir This allows the filter to be cleaned or replaced before the...

Страница 29: ...1 0 841 0 control 1 programme analogue input 4 0 1 0 842 set point analogue input 4 programme 0 100 50 843 min setting analogue input 4 0 99 0 844 max setting analogue input 4 0 100 100 845 0 positiv...

Страница 30: ...3 seconds on and untill InR appears on the CC Ease panel In programming mode the bypass and pre heater valves are always closed After 30 minutes the ComfoAir automatically termi nates the programming...

Страница 31: ...ed edge to ensure a good seal Pull the strap E to remove the heat exchanger and the leakage tray F E F Remove the heat exchanger from the leakage tray F The heat exchanger may contain water resi dues...

Страница 32: ...t using a damp cloth Install all parts in reverse order Carry out the self test in accordance with menu P76 The hollow side of the pre heater filter must face the pre heater holder Fasten the screws t...

Страница 33: ...wnwards Reconnect the power Press until malfunction disappears E1 E2 Exhaust supply fan malfunction Remove filters front and metal cover Does the fan connection on the PCB register 230 VAC Yes Activat...

Страница 34: ...T2 T3 T4 Disconnect the power Remove filters front and metal cover Remove the malfunctioning sensor s connector from the PCB Check the resistance of the malfunctioning sensor according to the adjacent...

Страница 35: ...es Yes Replace cog No Disconnect the power and replace PCB ATTENTION Reset unit Disconnect the power and replace motor ATTENTION Risk of electrocution do not touch the PCB the pre heater or the afterh...

Страница 36: ...Disconnect the power Remove filters front and metal cover Unplug Pre heater from the PCB Is resistance of Pre heater plug 300 ohms Yes Remove exchanger and Pre heater Is resistance of Pre heater cable...

Страница 37: ...anger Fan dirty Clean the fan Ventilation ducts blocked Clean the ventilation ducts ComfoAir is in frost protection opera tion Too noisy Fan bearings defective Replace the fan bearings Fan settings Ch...

Страница 38: ...rature sensor T1 T3 in top of unit near the electronic carriage 400300025 4 Temperature sensor T2 T4 in scroll casing of both fans 400300026 5 Forst free element 400300027 6 Filter 2x 400100030 7 Filt...

Страница 39: ...ite Yellow 0 10V Blue Green Yellow Green Yellow RS232 PC GND 12V Eb Ea GND 12V 12V Ab CCb Aa CCa GND GND Ext Comm N L3 PE Comm Basis RS232 KFB 12V RX TX ERR GND OFF BS GND GND FIE CH GND GND Tch Tge G...

Страница 40: ...White Brown White Brown White Yellow 0 10V Blue RS232 PC GND 12V Eb Ea GND 12V 12V Ab CCb Aa CCa GND GND Ext Comm N L3 PE Comm Basis RS232 KFB 12V RX TX ERR GND OFF BS GND GND FIE CH GND GND Tch Tge...

Страница 41: ...erial number where available Location of fan units 1 2 3 4 5 1 3 Installation Engineer s Details Engineer s Name Company Address Line 1 Address Line 2 Telephone Number Post Code 1 4 Commissioning Engi...

Страница 42: ...ystem installation clauses been followed as details in Tables 1 3 5 and 7 as applicable Yes No If any deviation from Tables 1 3 5 and 7 these should be detailed here Description of installed controls...

Страница 43: ...tection packaging been removed including background ventila tors such that system is fully functional Yes No For ducted systems has the ductwork installation been installed in such manner that air res...

Страница 44: ...Table 5 1a in ADF Extract Fan 1 Extract Fan 2 Extract Fan 3 Extract Fan 4 Extract Fan 5 For kitchen extract canopies only the highest setting needs to be recorded 3 3 Air Flow Measurements Extract Sys...

Страница 45: ...l s Refer to Table 5 1b ADF Measured Air Flow Low Rate l s Design Air Flow Low Rate l s Refer to Table 5 1b in ADF Living Room 1 Living Room 2 Dining Room Bedroom 1 Bedroom 2 Bedroom 3 Bedroom 4 Bedr...

Страница 46: ...694 Company register Zwolle 05022293 EG declaration of conformity Machine description Heat recovery units ComfoAir range Complies with the following directives Machinery Directive 98 37 EG Low Voltage...

Страница 47: ...1 43...

Страница 48: ...1 44 Zehnder Comfosystems Unit 1 Brookside Avenue Rustington West Sussex BN16 3LF J E Stork Ventilatoren B V 849050686 0709...

Отзывы: